VEGASON 51K … 53K
Set-up
Parameter adjustment/Adjustment
• Now choose the menu "Parameter adjust-
ment“.
In the menu "Instrument data/Parameter ad-
justment“ you now carry out all important
sensor adjustments. In the heading you now
see the previously entered measurement
loop name and the measurement loop de-
scription.
• First choose "Adjustment“.
• Click on "Min/Max-adjustment“.
You can carry out the Min/Max-adjustment
with medium or without medium. Generally
you will carry out the adjustment without me-
dium. When you want to carry out the adjust-
ment with medium, you have to carry out the
min.-adjustment with emptied vessel and the
max.-adjustment with filled vessel.
It is convenient and quick to carry out the
adjustment without medium as shown in the
example.
• Choose whether you want to make the
adjustment in m or in ft.
• Enter a distance for the upper and lower
level and the filling degree in % corre-
sponding to the distance.