40
VEGASON 51K … 53K
You have connected the PC with the adjust-
ment software VVO to your measuring sys-
tem.
• First of all siwtch on the power supply of
the connected sensor.
In the first 10 … 15 seconds the sensor starts
to take a current of approx. 22 mA (self-check)
and then takes a level proportional or distance
proportional current of 4 … 20 mA.
• Switch on the PC and start the adjustment
software VVO.
• Choose the point "Planning“ on the en-
trance screen with the arrow keys or the
mouse an click on "OK“.
You are asked for the user identification.
Set-up
• Enter under name "VEGA“.
• Also enter under password "VEGA“.
The adjustment program VEGA Visual Ope-
rating (VVO), called in the following VVO gets
into contact with the connected sensor …
… and indicates after a few seconds if and
with which sensor a connection exists.
The preadjusted user identification can be
modified later in the menu "User access“.