3 Mounting
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
In vessels with conical bottom it can be advantageous to mount the
device in the centre of the vessel, as measurement is then possible
down to the bottom.
Fig. 4: Mounting of the radar sensor on vessels with conical bottom
Mount the instrument at least 200 mm (7.874 in) away from the vessel
wall.
200 mm
(7.87")
Fig. 5: Mounting the radar sensor on the vessel top
Note:
If you cannot maintain this distance, you should carry out a false
signal suppression during setup. This applies especially if buildup on
the vessel wall is to be expected.
2)
Mounting position - bulk
solids
2)
In this case, it is recommended to repeat the false signal suppression at a
later time with existing buildup.