13
5 Set up with the display and adjustment module
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66376-EN-220111
on the reference plane can be found in chapter "
Technical data
". The
actual filling height is then calculated on the basis of these entries.
The actual product level during this adjustment is not important,
because the min./max. adjustment is always carried out without
changing the product level. These settings can be made ahead of
time without the instrument having to be installed.
Proceed as follows:
1. Select with
[->]
the menu item Distance A (max. value) and con-
firm with
[OK]
.
2. Edit the percentage value with
[OK]
and set the cursor to the
requested position with
[->]
.
3. Set the requested percentage value with
[+]
and save with
[OK]
.
The cursor jumps now to the distance value.
4. Enter the corresponding distance value in meters for the full ves-
sel.
5. Save settings with
[OK]
and move with
[ESC]
and
[->]
to Min.
adjustment.
Proceed as follows:
1. Select with
[->]
the menu item "
Distance B (min. value)
" and
confirm with
[OK]
.
2. Edit the percentage value with
[OK]
and set the cursor to the
requested position with
[->]
.
3. Set the requested percentage value with
[+]
and save with
[OK]
.
The cursor jumps now to the distance value.
Distance A (max. value)
Distance B (min. value)