6 Set up the sensor with the display and adjustment module
VEGADIF 85 • Profibus PA
53569-EN-230814
As input signals, the output values of Transducer Block (TB) can be
selected.
In the menu item "
Scaling unit
" you define the scaling variable and
scaling unit of the output value of FB 1.
In the menu item "
Scaling
", you assign the min. and max. values of
the input signal (Channel) to the respective values of the output (Out
Scale). The units correspond to the previous selection.
Min. values for PV lin Proc. and Out Scale process pressure in bar:
Max. values for PV lin Proc. and Out Scale process pressure in bar:
To damp process-dependent measured value fluctuations, set an
integration time of 0 … 999 s in this menu item. The increment is 0.1 s.
The default setting is a damping of 0 s.
In the menu item "
Lock/unlock adjustment
" you safeguard the sensor
parameters against unauthorized or unintentional modifications.
With active PIN, only the following adjustment functions are possible
without entering a PIN:
AI FB1 - scaling unit
AI FB1 - scaling
AI FB1 - damping
Lock/Unlock adjustment