C
opy sensor data
?
B
asic adjustment
I
f the
"
R
eset
"
is carried out
,
the sensor resets the values of the
following menu items to the reset values
(
see chart
):
7
)
M
enu section
F
unction
R
eset value
B
asic settings
U
nit of measurement
bar
T
emperature unit
°
C
Z
ero
/
M
in
.
adjustment
M
easuring range begin
S
pan
/
M
ax
.
adjustment
M
easuring range end
D
ensity
1
kg
/
l
D
ensity unit
kg
/
l
D
amping
0
s
L
inearisation
linear
S
ensor
-
TAG
S
ensor
D
isplay
D
isplayed value
PA
-
O
ut
S
ervice
A
dditional
PA
value
S
econdary
V
alue
1
O
ut
-
S
cale
-
U
nit
V
olume
/
l
S
caling
0
.
00
to
100
.
0
D
ecimal point indication
8888
.
8
T
he values of the following menu items are
not
reset with
"
R
eset
:
M
enu section
F
unction
R
eset value
B
asic settings
P
osition correction
no reset
D
isplay
L
ighting
no reset
S
ervice
L
anguage
no reset
A
pplication
no reset
F
actory setting
L
ike basic adjustment
,
furthermore special parameters are reset to
default values
.
8
)
P
ointer
T
he min
.
and max
.
distance values are reset to the actual value
.
A
dditional adjustment and diagnosis options such as e
.
g
.
scaling
,
simulation or trend curve presentation are shown in the following menu
schematic
.
Y
ou will
fi
nd a detailed description of these menu items in
the operating instructions manual
"
I
ndicating and adjustment module
"
.
7
)
S
ensor
-
speci
fi
c basic adjustment
.
8
)
S
pecial parameters are parameters which are set customer
-
speci
fi
cally on
the service level with the adjustment software
PACT
ware
.
R
eset
O
ptional settings
40
VEGABAR
65
•
P
ro
fi
bus
PA
6
S
et up with the indicating and adjustment module
PLICSCOM
28253
-
EN
-