3
L
oop the connection cable through the cable entry on the housing
base
1
)
I
nformation
:
T
he cable gland can be mounted in three positions each displaced by
90
°
.
S
imply exchange the cable gland against the blind plug in the
suitable thread opening
.
4
C
onnect the wire ends as described under
"
S
ingle
/
D
ouble
chamber housing
"
according to the numbering
5
C
onnect the screen to the internal ground terminal
,
connect the
outer ground terminal above on the housing to potential equal
-
isation
6
T
ighten the compression nut of the cable entry
.
T
he seal ring must
completely encircle the cable
7
A
ttach the mounting plate again and tighten the screws
T
he electrical connection of the sensor to the external housing is
hence ready
.
1
)
T
he connection cable is already preconfectioned
.
I
f necessary
,
shorten it to
the requested length
,
cut the breather capillaries clean
.
R
emove approx
.
5
cm of the cable mantle
,
strip approx
.
1
cm insulation from the ends of the
individual wires
.
A
fter shortening the cable
,
fasten the type plate with sup
-
port back onto the cable
.
VEGABAR
65
•
P
ro
fi
bus
PA
19
5
C
onnecting to power supply