C
urrent value
10
m
A
,
±
0
.
5
m
A
D
ynamic behaviour output
R
un
-
up time approx
.
10
s
90 %
100 %
10 %
t
t
T
A
t
t
S
2
1
F
ig
.
28
:
S
udden change of the process variable
,
dead time t
T
,
rise time t
A
and step response time t
S
1
P
rocess variable
2
O
utput signal
D
ead time
≤
150
ms
R
ise time
≤
100
ms
(
10
…
90
%
)
S
tep response time
≤
250
ms
(
ti
:
0
s
,
10
…
90
%
)
D
amping
(
63
%
of the input variable
)
0
…
999
s
,
adjustable
I
nput variable
A
djustment
A
djustment range of the min
./
max
.
adjustment relating to the nominal measuring range
:
-
percentage value
-
10
…
110
%
-
pressure value
-
20
…
120
%
A
djustment range of the zero
/
span adjustment relating to the nominal measuring range
:
-
zero
-
20
…
+
95
%
-
S
pan
-
120
…
+
120
%
10
)
-
D
i
ff
erence between zero and span
max
.
120
%
of the nominal range
R
ecommended max
.
turn down
10
:
1
(
no limitation
)
N
ominal measuring ranges and overload capability in bar
/
k
P
a
10
)
V
alues less than
-
1
bar cannot be set
.
VEGABAR
65
•
P
ro
fi
bus
PA
53
10
S
upplement
28253
-
EN
-
081209