7 Set up with the integrated display and adjustment unit
VEGABAR 38 • Three-wire with IO-Link (2 x transistor or 4 … 20 mA plus 1 x transistor)
57532-EN-191014
In this menu item, the min. and max. values for pressure, measuring
cell temperature and electronics temperature are displayed.
Menu item code:
•
LO
•
HI
Information:
To reset the pointer function, the VEGA Tools app or PACTware/DTM
is required.
This menu item displays the hardware and software status as well as
the serial number of the device.
Menu item code:
•
INF
Parameter:
•
HW
•
SW
•
SN
In this menu item you simulate switching states of the transistor out-
puts or current values of the 4 … 20 mA output. This allows the signal
path to be tested, e.g. via downstream display instruments or the
input card of the control system. The simulation values are: Pressure,
current, switching status.
Note:
Make sure the connected downstream devices are activated during
the simulation.
Menu item code:
•
SIM
Parameter:
•
Numerical value for pressure or current
•
Open or closed for switching output
Peak value indicator
Sensor information
Simulation