26
7 Set up with the integrated display and adjustment unit
VEGABAR 38 • Three-wire with IO-Link (2 x transistor or 4 … 20 mA plus 1 x transistor)
57532-EN-191014
Menu item
Code acc. to
VDMA 24574-1
Basic settings
Bluetooth access code
BT
Device-specific
access code
Protection of the parameterization
COD
Deactivated
Reset
RES
-
Menu item
Code acc. to
VDMA 24574-1
Delivery status
Status
STA
-
Parameter modification counter
PCO
-
Min. value pointer function
LO
Last values
Max. value pointer function
HI
Sensor information
INF, HW, SW
-
Simulation
SIM
-
The menu items are described below and comply with the technical
regulation VDMA 24574-1.
7.4 Parameter adjustment
7.4.1 Main menu
With the first setup, the instrument offers you a selection of the menu
languages. The selection you are making here can be changed any
time under "
Extended functions
", "
Menu language
".
In this menu item, the switching and reset points for hysteresis func-
tion and the lower and upper values for window function are defined
depending on the selected output function.
Hysteresis function
With the hysteresis function (HNO and HNC), the output changes its
state when the measured variable has reached the switching point
(SP). If the measured variable falls below the reset point (RP), the
output returns to its previous state.
Diagnostics
Selection language
Switching points