RS-232 Commands
Function Code: 882
49
Function Code: 882
Function Type:
Initialize Communication Port Data
Version 1
Command Format:
Set:
Inquire:
Display:
<SOH>S882CC149
Display:
<SOH>I882CC
Computer:
<SOH>s882CC149
Computer:
<SOH>i882CC
Notes:
1.
149
-
This verification code must be sent to confirm the command
Typical Response Message, Display Format:
<SOH>
I882CC
CC BBBBB P S D T AA
<ETX>
Typical Response Message, Computer Format:
<SOH>i882CC0000000000CCBBBBBPSD0AA&&CCCC<ETX>
Notes:
1.
0000000000
- Not Used.
2.
CC
- Communication Port Number (1)
3.
BBBBB
- Baud Rate (Decimal)
4.
P
- Parity (Decimal; 0= None, 1 or 2)
5.
S
- Stop Bit (Decimal; 1 or 2)
6.
D
- Data Bit (Decimal; 7 or 8)
7.
0
- Not Used
8.
AA
- Number of Rings before Answer (Decimal)
9.
&&
- Data Termination Flag
10.
CCCC
- Message Checksum