RS-232 Commands
Function Code: 50D
33
Function Code: 50D
Function Type:
Set Print Temperature Compensation Flag
Version 1
Command Format:
Set:
Inquire:
Display:
<SOH>S50D00f
Display:
<SOH>I50D00
Computer:
<SOH>s50D00f
Computer:
<SOH>i50D00
Typical Response Message, Display Format:
<SOH>
I50D00
f
<ETX>
Typical Response Message, Computer Format:
<SOH>i50D000000000000f&&CCCC<ETX>
Notes:
1.
0000000000
-
Not Used
2.
f
-
Print Temperature Compensation Flag
0 = Disable
1 = Enable
3.
&&
-
Data Termination Flag
4.
CCCC
-
Message Checksum