32
Setup
Automatic Events: (Pump Mode = Pump Sense)
i. Configure/ Enable Relay
ii. Set the Type to Standard
b. Via:
Setup > Automatic Events > Device Tasks
:
a. Add a task for each Dispenser Relay:
i. Set the Device to the Relay
ii. Select each required Hose Alarm for the appropriate Gasoline Hose(s) as a Trigger
Figure 47. Example Device Task – TLS Pump Control (With Dispenser Relay(s))
Automatic Events: (Pump Mode = Pump Sense)
These are the steps required for ISD Shutdown If pump mode selected = Pump Sense.
Available Pump Modes in
Setup > Pumps and Lines > Pumps
:
Pump Sense
: The console senses if the pump is active when a pump request signal is sent to turn on/off the
pump (this signal also acts as a tank "active" signal to the console).
PUMP MODE = PUMP SENSE
1. For each Pump on a Gasoline Line:
a. Via:
Setup > Devices > Relay
:
i. Configure/Enable a Relay to supply power to pump control device
ii. Set the Type to Standard
b. Via:
Setup > Devices > External Input
:
i. Configure/Enable an External Input (Pump Sense) for the pump
ii. Set the Type to Pump Sense
c. Via: Setup > Pumps and Lines > Pumps:
i. Configure/Enable a Pump
ii. Set the Mode to Pump Sense
iii. Assign the appropriate Tank to Pump
iv. Set the Pump Sense to the appropriate External Input
2. For each Gasoline Line: