34
Setup
Automatic Events: (Pump Mode = Pump Sense)
ii. Set the Type to Standard
b. Via:
Setup > Automatic Events > Device Tasks
:
Add a task for each Dispenser Relay:
i. Set the Device to the Relay
ii. Set each required Hose Alarm for the appropriate Gasoline Hose(s) as a Trigger
Figure 50. Example Device Task – Pump Sense (With Dispenser Relay(s))