31
Setup
Automatic Events: (Pump Mode = TLS Pump Control)
c. Via:
Setup > Pumps and Lines > Pumps
:
i. Configure/Enable a Pump
ii. Set the Mode to TLS Pump Control
iii. Assign the appropriate Tank to the Pump
iv. Set the Pump Control to the appropriate Relay
v. Set the Pump Sense to the appropriate External Input
2. For each Gasoline Line:
a. Via:
Setup > Pumps and Lines > Lines
:
i. Configure/Enable a Line
ii. Assign the appropriate gasoline Pump(s) to the Line
b. Via:
Setup > Automatic Events > Device Tasks
:
Add a task for required ISD Site Alarms
California Air Resources Board (CARB) requires that gasoline dispensing be shutdown for
specific ISD Site alarms and Hose alarms (See Table 3 on page 5).
i. Set the Device to the Gasoline Line
ii. Select each required ISD Site Alarm as a Trigger
iii. Hose Site Shutdown Option (if available): select the Hose Alarms for each Gasoline Hose as a Trigger
Figure 46. Example Device Task – TLS Pump Control (No Dispenser Relay(s))
3. Dispenser Relay Shutdown Option: For each Dispenser Relay:
a. Via:
Setup > Devices > Relay
: