35
Specifications
Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating the ProtoNode.
•
The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature
range.
•
The interconnecting power connector and power cable shall:
- Comply with local electrical code
- Be suited to the expected operating temperature range
- Meet the current and voltage rating for the ProtoNode
•
Furthermore, the interconnecting power cable shall:
- Be of length not exceeding 3.05m (118.3”)
- Be constructed of materials rated VW-1, FT-1 or better
•
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed in
a Restricted Access Area requiring a key or a special tool to gain access.
•
This device must not be connected to a LAN segment with outdoor wiring.
Table 6. Specifications
Electrical
Connections
One 3-pin Phoenix connector with: RS-485/RS-232 (Tx+ / Rx- / gnd)
One 3-pin Phoenix connector with: RS-485 (Tx+ / Rx- / gnd)
One 3-pin Phoenix connector with: Power port (+ / - / Frame-gnd)
One Ethernet 10/100 BaseT port
Power
Requirements
Input Voltage: 9-30VDC or 24VAC Current draw: 24VAC 0.125A
Max Power: 3 Watts 9-30VDC .25A @12VDC
Approvals
CE and FCC part 15 B, UL 60950-1, CAN/CSA C22.2, BTL marked, WEEE
compliant, RoHS3 compliant, Modbus and DNP 3.0 conformance tested, REACH
compliant, UKCA compliant
Physical
Dimensions
4 x 1.1 x 2.7 in (10.16 x 2.8 x 6.8 cm)
Weight
0.4 lbs (0.2 Kg)
Operating
Temperature
-20°C to 70°C (-4°F to158°F)
Humidity
10-95% RH non-condensing