Installation
Starting the System and Completing the Installation
15
Disconnect, lock out, and tag power at the panel before servicing the pump
When servicing equipment, use non-sparking tools and use caution when removing or
installing equipment to avoid generating a spark.
Table 2. Pump Length Requirements
Bury
Depth
“A”
Riser Length
“B”
Tank Diameters “C” / Pump Length Requirements “D”
30”
10” (883-442-1)
C = 72” / D = 78”
C = 84” / D = 90”
C = 96” / D = 102” C = 120” / D = 126” C = 144” / D = 150”
36”
16” (883-445-1)
C = 72” / D = 84”
C = 84” / D = 96”
C = 96” / D = 108” C = 120” / D = 132” C = 144” / D = 156”
42”
21” (883-449-1)
C = 72” / D = 89” C = 84” / D = 101” C = 96” / D = 113” C = 120” / D = 137” C = 144” / D = 161”
48”
27” (883-449-1)
C = 72” / D = 95” C = 84” / D = 107” C = 96” / D = 119” C = 120” / D = 143” C = 144” / D = 167”
60”
36” (883-451-1) C = 72” / D = 104” C = 84” / D = 116” C = 96” / D = 128” C = 120” / D = 152” C = 144” / D = 176”
72”
51” (883-454-1) C = 72” / D = 119” C = 84” / D = 131” C = 96” / D = 143” C = 120” / D = 167” C = 144” / D = 191”
Table 3. Winding Resistances
Model Number
Pump Motor
Assembly
HP
Volt
Phase
Winding Resistances (Ohms)
Orange to Red
Orange to
Black
Red to Black
Blue to Blue
UMP300J4-2HB
3
208-230
3
1.8 - 2.2
1.8 - 2.2
1.8 - 2.2
0.0 - 1.0
UMP300J17-3HB
3
380-415
3
7.1 - 8.7
7.1 - 8.7
7.1 - 8.7
0.0 - 1.0
UMP500J4-2K
5
208-230
3
1.2 - 1.5
1.2 - 1.5
1.2 - 1.5
0.0 - 1.0
UMP500J17-3K
5
380-415
3
4.5 - 5.5
4.5 - 5.5
4.5 - 5.5
0.0 - 1.0
UMP500J6-2K
5
575
3
6.6 - 8.2
6.6 - 8.2
6.6 - 8.2
0.0 - 1.0
NOTE: The above readings do not include the added resistance of the power supply wires to the submersible pump. Therefore, for
the readings to fall within the above limits, the resistance should be checked at the submersible pump junction box. If the resis
-
tance readings are taken at the control box or magnetic starter, they will be sightly higher.