TCY-T0121 Intelligent Compact Controller

 

  

Version: 2004-07 

[email protected] 

Page 2/12 

Control Functions 

The compact controller TCY operates with four different control modules. These modules can be activated and 

parameterized according to the application to be controlled. The main modules are: Temperature PI, Temperature 

On/Off, Universal PI and Universal On/Off. All modules operate simultaneously. In order to use the controller, at 

least one control module must be enabled. The outputs that respond to each control loop need to be assigned in the 

output section. 

Temperature Control Module 

HC -00: 2-pipe or 4-pipe system. Select 2-pipe system if the system has only a single coil that operates as heater in 

winter and cooling device in summer. Select 4-pipe system, if specific heating and cooling coils are available. 
HC -01: Dead Zone Span. The cooling setpoint W

C

 consists of the heating setpoint and the dead zone span. Changing 

the cooling setpoint in 2-pipe mode therefore changes as well the heating setpoint. The factory setting for the dead 

zone span is 1K. 

Modulating PI-Control 

The temperature PI control mode is enabled with parameter HC -02. The controller maintains the temperature set 

point by calculating the output position based on proven PI control algorithms.  

Control parameters:  

HC -03, HC -04: P-bands for heating and cooling are programmable. The factory setting is 2 K. The p-bands are 

disabled if 0 is selected. 
HC -05: A large I part increases the swinging tendency of the control loop. Limiting the integral part may reduce this 

tendency. The I-part is disabled if 0 is selected. 
HC -06: Tn, Reset time of Analog loop integral. Tn is the time needed for the integral to run from 0 to 100%. The 

range is 0.5 – 30 min. The setting depends on the control application. For temperature control of a medium sized 

room, a setting of 5-10 minutes is appropriate. For pressure control on a VAV box a value of 3 minutes is 

recommended, depending on the speed of the actuator.  
 
 
 
 
 
 
 
 

Room Temperature 

 

W

H

 

Setpoint Heating 

X

PH

 

Proportional Band Heating  

W

C

 

Setpoint Cooling = W

H

 + X

DZ

  

X

PC

 

Proportional Band Cooling  

Y

H

 

Output signal Heating 

X

DZ 

Dead zone 

 

 

Y

C

 

Output signal Cooling 

Tn 

Reset time of Integral 

 

Y

I

 

Integral part of output signal 

Temperature On/Off control 

The control mode is enabled with parameter HC -07. On/Off control is suitable to operate fan coil valves and reheat 

or cooling compressor stages. By providing the dry Normally Open contact, any voltage from 10…250V for actuators 

and switching stages may be used. Switching power is limited to 0.5A per stage.  
Control parameters: 
HC -08: Enables a second stage for reheat. HC -09: Enables a second compressor stage for cooling. 
HC -10, HC -11: The switching span determines the temperature difference required for the next heating stage to be 

activated. 
HC -12: The hysteresis defines when a heating stage is switched off. The aim is to avoid unnecessary switching of 

heating stages thus increasing the life span of involved equipment as well as saving energy. 
Delayed switching. The upper heating/ cooling stages will not switch on at the same time. The higher stage will not 

start earlier than 5 seconds after the lower stage has been initiated.  
 
 
 
 
 
 
 
 
 

 
H

RC

 

Hysteresis Heating/Cooling 

X

RC

 

Switching Span Heating/Cooling 

Y

H

 [%] 

100

0

X

PH

 

W

X

PC

 

X

DZ

 

Heating Mode 

Cooling Mode 

T [K] 

Y

C

 [%] 

W

Y

I

 [%] 

100

0

T n 

W

X

 

I Control Part 

t [min] 

Stage 2  
 

Heating 

Stage 1  
 

0

X

RC

 

W

H

 

On/off Control 

T [K] 

H

RC

 

W

C

 

Cooling 

X

DZ

 

Summary of Contents for TCY-T0121

Page 1: ...mation system Internal or external passive temperature sensor selectable by switch Transformation of display value according to analog sensor range Password protected programmable user and control parameters Display and operation unit available in various designs and materials Applications Air Only Systems Constant or Variable Air Volume systems for single or dual duct systems with options of o up...

Page 2: ...set time of Analog loop integral Tn is the time needed for the integral to run from 0 to 100 The range is 0 5 30 min The setting depends on the control application For temperature control of a medium sized room a setting of 5 10 minutes is appropriate For pressure control on a VAV box a value of 3 minutes is recommended depending on the speed of the actuator T Room Temperature WH Setpoint Heating ...

Page 3: ...olved It should be at least 1 2 times the reaction time of the control cycle XU Input signal Xp1 Proportional Band reverse acting YU Output signal of universal loop Xp2 Proportional Band direct acting wR wD Reverse Direct Setpoint Tn Integral Reset Time XDZ Dead Zone Span 2 point control This control mode is enabled by parameter 1U 08 for the reverse signal and 1U 09 for the direct signal 2 point ...

Page 4: ...ching outputs DO1 and DO2 are factory assigned as floating output They may be assigned as digital outputs using OP 07 to OP 08 The digital outputs may be used either as switching outputs for Temperature or Universal ON OFF modules Each output needs to be assigned to a control loop See parameter OP section for details Time schedule on digital outputs The digital outputs may be used with an individu...

Page 5: ...hes the unit off UP and DOWN buttons change setpoints and parameters OPTION button used for accessing different control modes and advanced setup Acts as Enter in parameter changing menu Operation Modes Comfort The unit is in full operation mode All the control functions are operating according to their setpoints The unit displays occupied mode Standby The setpoints are shifted according to paramet...

Page 6: ...eatedly pressing the OPTION button until DO1 or DO2 is displayed in the large LCD digits Pressing UP DOWN steps through following modes ON OFF PROG selecting ON or OFF sets the output in manual mode the manual symbol is displayed Pressing the OPTION button for more than 3 seconds starts the schedule mode The schedule operation for the DO is similar to general time scheduling see below A total of 2...

Page 7: ... user is allowed to change operation modes OFF Disabled ON Enabled ON OFF ON UP 01 Choose if the end user is allowed to change set points OFF Disabled ON Enabled ON OFF ON UP 02 Choose if the end user is allowed to override secondary setpoint in cascade control OFF Disabled ON Enabled ON OFF ON UP 03 Heat Cool change Enable Choose if the end user is allowed to change heating cooling mode OFF Disab...

Page 8: ...erature loop is setpoint of analog loop ON Cascade Active OFF no cascade ON OFF OFF 1U 01 Dead zone for Universal Loop range acc to input Acc Input 0 1U 02 Enable PI Reverse Loop ON OFF OFF 1U 03 Enable PI Direct Loop ON OFF OFF 1U 04 P Band or Switching Span reverse acting Range according to input Selecting 0 disables the P part Acc input 10 1U 05 P Band or Switching Span direct acting Range acco...

Page 9: ...55 50 Mechanical Design and installation The unit consists of three parts The mounting plate the power case and the front part consisting of a module and an outside frame The outside frame may be replaced with a special design based on interior design and taste of the end user Please talk to your dealer regarding different designs materials and colors available Installation 1 Arrange the wires to ...

Page 10: ...puts AC Voltage Insulation resistance Optical coupled TRIAC DO1 DO2 24V 220V AC 1A max AC2500 V RMS acc to EN 60 730 1 complying with UL standards File ref E81734 Display LCD Actual values and setpoint Resolution value 1000 Resolution value 1000 Digital Signals 4 digits 0 1 1 ON OFF Parameters For details of control parameters see parameter section Environment Ambient Temperature 10 to 50 C acc IE...

Page 11: ... Analog Input Output Ground 2 Power Supply 24V AC 3 Digital Output 1 4 Digital Output 2 5 Temperature sensor NTC 6 Temperature sensor NTC 7 Analog Output 1 0 10V or 0 20mA 8 Analog Input 1 0 10V 0 5V or 0 20mA The switch for internal external temperature setting is located on the back of the operation terminal AI1 JP2 0 10V DC 0 5V DC 0 20 mA AO1 JP1 0 10V DC 0 20 mA 1 4 3 4 2 3 1 2 2 3 1 0V AC GN...

Page 12: ...ion advice or training in how to use our products The target is to optimize your benefits The only thing you need to do is Talk to us Quality Support Partnership Our Offer Your Call Tel 86 10 6786 9251 3 Fax 86 10 6786 9256 Email info vectorcontrols com VECTOR CONTROLS LTD 23 Xi Huan Bei Road Room 208 Hua Teng Fa Zhan Building Yi Zhuang Beijing 100176 PRC VECTOR ...

Reviews: