SDC-C1 Duct CO2-transmitter

 

Features 

 

CO2 measurement for air ducts 

 

Minimum and maximum value memory 

 

0…10V, 0…20mA or 2…10V, 4…20mA measuring signals 

selectable with jumpers 

 

Optional alternative signal ranges programmable 

 

May be used as simple P-controller 

 

Selectable averaging signal

 

 

Optional internal or external display (OPC-S or OPA-S)

 

 

Status LED

 

Applications 

 

Demand based ventilation for homes and offices based on 
measurement of the CO2 concentration 

 

Preset standard measuring range 0...2000 ppm, max 

possible range 0...5000 ppm 

 

Recording of minimum and maximum limits for critical environments 

 

Direct control of extraction fan 

CO2 transmitter 

The CO2 concentration is measured through non-dispersive infrared (NDIR) waveguide technology with ABC automatic 

background calibration algorithm. The applied measuring technology guarantees excellent reliability and long-term 

stability. The microprocessor samples the CO2 once per second. It calculates an averaging signal over a preset number of 

samples and generates the output signal. 

The output signal range and type may be customized by jumpers and if required by a programming module. Standard 

signal ranges are 0-10 VDC, 2-10 VDC, 4-20 mA and 0-20 mA. Other ranges can be defined by using the external display 

and programming module (OPA-S). 

 

For OPA-S, OPC-S 

usage see section 

Parameter configuration

 on page

 5. 

Automatic baseline calibration (ABC) 

The ABC background calibration constantly supervises the measured CO2 concentrations. The calibration function expects 

the CO2 values sink to 400 ppm when the room is not occupied. Over a period of several days the controller tries to reach 

this value step by step through recalibration of 30ppm per day max. In order to reach the given accuracy, it is required 

that the sensor is for at least 3 weeks in operation. 

 

NOTE: The ABC calibration works only in those applications where the CO2 concentration sinks regularly to fresh air 

levels of 400 ppm. For special applications such as green houses, animal farms, etc. the ABC calibration should be 

de-activated and the sensor should be manually calibrated. The automatic calibration can deactivate through the 

external operation terminal. See chapter parameter configuration for details. The Sensor can be calibrated by the 

client and does not need to be sent in for calibration. For manual calibration see section 

Calibration

 on page 7. 

Minimum and maximum values 

Using a display & programming module OPA-S or the optional built-in display and operation terminal OPC-S, the user has 

the option to read out and reset minimum and maximum CO2 values. The minimum and maximum values may as well be 
used as output signals. The minimum and maximum values are automatically saved to the device and are available after a 

power interruption. 

 

For OPA-S, OPC-S 

usage see section 

Displaying minimum and maximum values

 on pag

4. 

Safety 

 

DANGER! Safety advice 

This device is for use as a CO2 concentration indicator and CO2 transmitter for comfort applications. It is not a 

safety device. Where a device failure could endanger human life and property, it is the responsibility of the client, 

installer and system designer to add additional safety devices to prevent such a device failure. Ignoring 

specifications and local regulations may cause equipment damage and endangers life and property. Tampering 

with the device and misapplication will void warranty. 

Types and Ordering 

Product Name 

Product Nr. 

Description/Option 

CO2 Sensor

 

SDC-C1-16-1 

40-300152 

CO2 transmitter for air ducts, 160 mm probe, incl. cable gland AMC-1 

Accessories

 

OPC-S 

40-500029 

Built-in display and operation terminal. 

OPA-S 

40-500006 

External display and operation terminal. 

Note: For the correct display of values, V1.7 and later is required. 

AMC-2 

40-500074 

Conduit connector: NPT thread 

 

 

Summary of Contents for SDC-C1

Page 1: ...er to reach the given accuracy it is required that the sensor is for at least 3 weeks in operation NOTE The ABC calibration works only in those applications where the CO2 concentration sinks regularly...

Page 2: ...tputs Analog outputs Output signal Resolution Maximum load 0 10 VDC 0 20 mA or 2 10 VDC 4 20 mA 10 bit 9 7 mV 0 019 5 mA Voltage signal 1k current signal 250 Environment Operation Climatic conditions...

Page 3: ...ion on page 5 Mounting instruction See SDC C1 installation sheet no 70 000573 www vectorcontrols com Dimension mm inch 2 10V 4 20mA 0 10V 0 20mA Range STATUS LED OPA S VDC mA AO1 JP4 JP1 OPC S Sensor...

Page 4: ...the UP key for at least 5 seconds and wait until the value changes Use of OPC S 1 Press the UP key to see the maximum values or the DOWN key to see the minimum values 2 To reset the minimum value pre...

Page 5: ...he UP and DOWN keys to set the password 0009 and confirm with the RIGHT key 5 Select IP SEL Input Parameter or OP SEL Output Parameter with UP and DOWN and confirm with the RIGHT key The first paramet...

Page 6: ...ameter Description Range Default OP 00 AO1 CO2 Configuration of output signal 0 CO2 value 1 Recorded minimum CO2 value 2 Recorded maximum CO2 value 0 2 0 OP 01 AO1 CO2 Minimum limitation of CO2 output...

Page 7: ...r level of CO2 could prevent a stable signal Observe the CO2 value on the OPA S 2 Once the CO2 value has stabilized login with the OPA S and set IP 06 2 then exit configuration mode The air quality le...

Page 8: ...20405 Vector Controls GmbH Switzerland Page 8 8 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzer...

Reviews: