Doc: 70-00-0399A, V2.9, 20220405  

© Vector Controls GmbH, Switzerland  

Page 4-8 

Subject to change without notice  

www.vectorcontrols.com 

Operation 

Displaying minimum and maximum values 

To read out or reset the stored CO2 minimum and maximum values use the optional display & programming module 

OPA-S or the built-in display & operation terminal OPC-S. 
Use of OPA-S: 

1.

 

Open the SDC housing (see SDC-C1 installation sheet 70-000573 

www.vectorcontrols.com

). 

2.

 

Connect the OPA-S operating device to the OPA-

S connector on the SDC (see section 

Wiring and Connection

 on 

page 3). The measured CO2 value is displayed. 

3.

 

Press the “UP” key to see the maximum values or the

 

“DOWN” key to see the minimum values.

 

4.

 

To reset the minimum value, press the “DOWN” key for at least 5 seconds and wait until the value changes.

 

5.

 

To reset the maximum value, press the “UP” key for at least 5 seconds and wait until the value changes.

 

 

Use of OPC-S: 

1.

 

Press the “UP” key to see the maximum values or the “DOWN” key to see the minimum values.

 

2.

 

To reset the minimum value, press the “DOWN” key for at least 5 seconds and wait until the value changes.

 

3.

 

To reset the maximum value, press the “UP” key for a

t least 5 seconds and wait until the value changes. 

 

Status-LED 

 

 

Error messages shown on OPA-S or OPC-S 

Error 

Description 

Err 1: 

Communication error: Verify cable connections, cable type and maximum distance. 

Err 2: 

CO2 sensor error: Make sure the sensor is not miss-calibrated. If possible, execute 400 ppm calibration. (see 

section 

Calibration

 on page 

7)

If error cannot be removed by calibrating the sensor, replace product. 

 

 

 

2-10V/4-20mA

0-10V/0-20mA

R

a

n

g

e

STATUS

LED

OPA-S

VDC

mA

A

O

1

J

P

4

J

P

1

OPC-S

Sensor

1

3

2

V+

G

N

D

A

O

1

24V

C

O

2

0V

Status LED 

- No light 

: No power or unit damaged 

- 5 sec flashing 

: Normal 

- 2 second blinking 

: Calibration 

- 10 second pulse 

: Calibration successful 

- Constant red > 10 sec 

: Calibration or sensor error 

 

Red Status-LED

 

Summary of Contents for SDC-C1

Page 1: ...er to reach the given accuracy it is required that the sensor is for at least 3 weeks in operation NOTE The ABC calibration works only in those applications where the CO2 concentration sinks regularly...

Page 2: ...tputs Analog outputs Output signal Resolution Maximum load 0 10 VDC 0 20 mA or 2 10 VDC 4 20 mA 10 bit 9 7 mV 0 019 5 mA Voltage signal 1k current signal 250 Environment Operation Climatic conditions...

Page 3: ...ion on page 5 Mounting instruction See SDC C1 installation sheet no 70 000573 www vectorcontrols com Dimension mm inch 2 10V 4 20mA 0 10V 0 20mA Range STATUS LED OPA S VDC mA AO1 JP4 JP1 OPC S Sensor...

Page 4: ...the UP key for at least 5 seconds and wait until the value changes Use of OPC S 1 Press the UP key to see the maximum values or the DOWN key to see the minimum values 2 To reset the minimum value pre...

Page 5: ...he UP and DOWN keys to set the password 0009 and confirm with the RIGHT key 5 Select IP SEL Input Parameter or OP SEL Output Parameter with UP and DOWN and confirm with the RIGHT key The first paramet...

Page 6: ...ameter Description Range Default OP 00 AO1 CO2 Configuration of output signal 0 CO2 value 1 Recorded minimum CO2 value 2 Recorded maximum CO2 value 0 2 0 OP 01 AO1 CO2 Minimum limitation of CO2 output...

Page 7: ...r level of CO2 could prevent a stable signal Observe the CO2 value on the OPA S 2 Once the CO2 value has stabilized login with the OPA S and set IP 06 2 then exit configuration mode The air quality le...

Page 8: ...20405 Vector Controls GmbH Switzerland Page 8 8 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzer...

Reviews: