Use the CO2-Transmitter as P-Controller 

The CO2-transmitter may be converted into a proportional fresh air controller through a simple change of two parameter 

settings: 

1.

 

Set a minimum CO2 concentration when the fresh air fan should start to run at its minimum speed for example 

500 ppm. Set this as the minimum value in 

IP 03

 parameter. 

2.

 

Then define the CO2 value when the fan should run at full speed, for example 1000 ppm and set this value in 

IP 04

. 

Your transmitter has now been converted into an air quality P-Controller! 
By using the analog output, the fan will start to run if the CO2 concentration is higher than 500 ppm. It increases to its 

maximum when CO2 concentration reaches 1000 ppm. 

 

Calibration 

The CO2 sensor unit is maintenance free in normal environments thanks to the built-in self-correcting ABC algorithm 

(Automatic Baseline Correction). This algorithm constantly keeps track of the sensor’s lowest reading over a 7 days 

interval and slowly corrects for any long-term drift detected as compared to the expected fresh air value of 400 ppm CO2. 

Rough handling and transportation might, however, result in a reduction of sensor reading accuracy. With time, the ABC 

function will tune the readings back to the correct numbers. The default “tuning speed” is however limited to about 30 

ppm/week. For post calibration convenience, in the event that one cannot wait for the ABC algorithm to cure any 

calibration offset, manual calibration may be activated using following procedure. There are two calibration possibilities: 0 

ppm and 400 ppm. Only one of the two manual calibration needs to be performed. 

Calibration to 400 ppm (Fresh air) 

1.

 

Connect OPA-S or use the optional built-in OPC-S and expose the active sensor for at least 5 minutes to fresh 

outside air. It is important to expose the sensor to only fresh air. An open window close to the sensor with a 

higher level of CO2 could prevent a stable signal. Observe the CO2 value on the OPA-S. 

2.

 

Once the CO2 value has stabilized, login with the OPA-S and set 

IP 06

 = 2, then exit configuration mode. The air 

quality led will blink green color 2 times alternating with the status led in 2 second intervals.  

3.

 

The sensor will now wait for a stable concentration. Once the calibration has been executed, the status LED will 

show constant RED and the green air quality led will blink for 10s if successful. If calibration is not successful (no 

stability of concentration for 5 min, no communication with sensor) the red air quality led will blink instead and 

the status LED will stay constantly on red in error mode. Recalibrate or restart device to stop error mode. 

4.

 

You may additionally verify the calibration using the OPA-S. If successful 

IP 06

 will change to 0. If unsuccessful 

the value of 

IP 06

 changes to 4. 

5.

 

If unsuccessful, wait at least 1 minute before repeating the procedure again. Make sure that the sensor 

environment is steady and calm! 

Calibration to 0 ppm with CO2 free gas 

1.

 

Connect OPA-S or use the optional built-in OPC-S and place the sensor in a container filled with a gas mixture 

which is free from CO2 (i.e., Nitrogen or Soda Lime CO2 scrubbed air). Observe the CO2 value on the OPA-S. 

2.

 

Once the CO2 value has stabilized, login with the OPA-S and set 

IP 06

 = 1, then exit configuration mode. The air 

quality LED will blink in red color 2 times alternating with the status led in 2 second intervals.  

3.

 

The sensor will now wait for a stable concentration. Once the calibration has been executed, the status LED will 

show constant RED and the green air quality led will blink for 10s if successful. If calibration is not successful (no 

stability of concentration for 5 min, no communication with sensor) the red air quality led will blink instead and 

the status LED will stay constantly on red in error mode. Recalibrate or restart device to stop error mode.  

4.

 

You may additionally verify the calibration using the OPA-S. If successful 

IP 06

 will change to 0. If unsuccessful 

the value of 

IP 06 

changes to 4. 

5.

 

If unsuccessful, wait at least 1 minute before repeating the procedure again. Make sure that the sensor 

environment is steady and calm! 

 

 

 

Summary of Contents for SDC-C1

Page 1: ...er to reach the given accuracy it is required that the sensor is for at least 3 weeks in operation NOTE The ABC calibration works only in those applications where the CO2 concentration sinks regularly...

Page 2: ...tputs Analog outputs Output signal Resolution Maximum load 0 10 VDC 0 20 mA or 2 10 VDC 4 20 mA 10 bit 9 7 mV 0 019 5 mA Voltage signal 1k current signal 250 Environment Operation Climatic conditions...

Page 3: ...ion on page 5 Mounting instruction See SDC C1 installation sheet no 70 000573 www vectorcontrols com Dimension mm inch 2 10V 4 20mA 0 10V 0 20mA Range STATUS LED OPA S VDC mA AO1 JP4 JP1 OPC S Sensor...

Page 4: ...the UP key for at least 5 seconds and wait until the value changes Use of OPC S 1 Press the UP key to see the maximum values or the DOWN key to see the minimum values 2 To reset the minimum value pre...

Page 5: ...he UP and DOWN keys to set the password 0009 and confirm with the RIGHT key 5 Select IP SEL Input Parameter or OP SEL Output Parameter with UP and DOWN and confirm with the RIGHT key The first paramet...

Page 6: ...ameter Description Range Default OP 00 AO1 CO2 Configuration of output signal 0 CO2 value 1 Recorded minimum CO2 value 2 Recorded maximum CO2 value 0 2 0 OP 01 AO1 CO2 Minimum limitation of CO2 output...

Page 7: ...r level of CO2 could prevent a stable signal Observe the CO2 value on the OPA S 2 Once the CO2 value has stabilized login with the OPA S and set IP 06 2 then exit configuration mode The air quality le...

Page 8: ...20405 Vector Controls GmbH Switzerland Page 8 8 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzer...

Reviews: