background image

 

SDC-C1 

D

UCT 

CO2

 

T

RANSMITTER

 

 

Doc: 70-00-0399A, V2.9, 20220405  

© Vector Controls GmbH, Switzerland  

Page 2-8 

Subject to change without notice  

www.vectorcontrols.com 

Technical Specifications 

 

Power supply 

Operating voltage 

24 VAC 50/60 Hz ± 10%, 24 VDC ± 10% 

Power consumption 

Max. 2 VA 

Safety extra-low voltage (SELV) 

HD 384, class II 

Connection 

Terminal connectors 

For wire 0.34…2.5 mm

2

 

(AWG 24…12)

 

CO2 measurement 

Sensing method  

Non-dispersive infrared (NDIR) waveguide technology 

with ABC automatic background calibration algorithm 

 

Sampling method 

Diffusion 

 

Response time (90%) 

2 Minutes 

 

Measurement range 

0 - 5000 ppm 

vol.

 

 

Repeatability 

± 20 ppm ± 1 % of measured value 

 

Accuracy 

± 40 ppm ± 3 % of measured value 

 

Pressure dependence 

+ 1.6 % reading per kPa deviation from normal 

pressure, 100 kPa 

Signal outputs 

Analog outputs 

Output signal 

Resolution 

Maximum load 

 

0

10 VDC, 

0…20

 mA 

or 2…10 V

DC

, 4…20 mA

 

10 bit, 9.7 mV, 0.019.5 mA 

Voltage s

ignal: ≥1kΩ, 

current s

ignal: ≤

2

50Ω

 

Environment 

Operation 

Climatic conditions 

Temperature 

Humidity 

To IEC 721-3-3 

class 3 K5 

0…

50 

°C (32…1

22 °F) 

<85% RH non-condensing 

 

Transport & storage 

Climatic conditions 

Temperature 

Humidity 

Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 

class 3 K3 and class 1 K3 

-3

0…70

 °C (-22

…158

 °F) 

<95% RH non-condensing 

class 2M2 

Standards 

Degree of protection 

IP30 to EN 60 529 

Safety class 

III (IEC 60536) 

Housing materials 

Cover, back part 

PC+ABS (UL94 class V-0) 

General 

Dimensions (H x W x D) 

Transmitter case 
Probe 

 
68 x 91 x 47 mm (2.7 x 3.7 x 1.9 in) 
Ø 14 x 160 mm, (Ø 0.55 x 6.2 in) 

 

Weight (including package) 

290 g (10.2 oz.) 

 

Product testing and certification 

 

Declaration of 

Conformity 

Information on the conformity of our products can be found on our website 

www.vectorcontrols.com

 on the corresponding product page under "Downloads". 

 

 

 

Summary of Contents for SDC-C1

Page 1: ...er to reach the given accuracy it is required that the sensor is for at least 3 weeks in operation NOTE The ABC calibration works only in those applications where the CO2 concentration sinks regularly...

Page 2: ...tputs Analog outputs Output signal Resolution Maximum load 0 10 VDC 0 20 mA or 2 10 VDC 4 20 mA 10 bit 9 7 mV 0 019 5 mA Voltage signal 1k current signal 250 Environment Operation Climatic conditions...

Page 3: ...ion on page 5 Mounting instruction See SDC C1 installation sheet no 70 000573 www vectorcontrols com Dimension mm inch 2 10V 4 20mA 0 10V 0 20mA Range STATUS LED OPA S VDC mA AO1 JP4 JP1 OPC S Sensor...

Page 4: ...the UP key for at least 5 seconds and wait until the value changes Use of OPC S 1 Press the UP key to see the maximum values or the DOWN key to see the minimum values 2 To reset the minimum value pre...

Page 5: ...he UP and DOWN keys to set the password 0009 and confirm with the RIGHT key 5 Select IP SEL Input Parameter or OP SEL Output Parameter with UP and DOWN and confirm with the RIGHT key The first paramet...

Page 6: ...ameter Description Range Default OP 00 AO1 CO2 Configuration of output signal 0 CO2 value 1 Recorded minimum CO2 value 2 Recorded maximum CO2 value 0 2 0 OP 01 AO1 CO2 Minimum limitation of CO2 output...

Page 7: ...r level of CO2 could prevent a stable signal Observe the CO2 value on the OPA S 2 Once the CO2 value has stabilized login with the OPA S and set IP 06 2 then exit configuration mode The air quality le...

Page 8: ...20405 Vector Controls GmbH Switzerland Page 8 8 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzer...

Reviews: