SDC-C1
D
UCT
CO2
T
RANSMITTER
Doc: 70-00-0399A, V2.9, 20220405
© Vector Controls GmbH, Switzerland
Page 5-8
Subject to change without notice
www.vectorcontrols.com
Configuration
Output signal configuration, Jumper settings
The analog output signal type for the AO1 output may be configured with jumper
JP1
for Voltage or Current control signals. The factory setting is Voltage.
For Jumper location see section “
” on page
The signal range may be set with jumper
JP4
for the analog signal output AO1.
JP4
will only operate if the output range specified with output parameter
of 0…100%.
With any other setting the
position of
JP4
has no influence and the signal range defined with the output
applies.
For Jumper location see section “
” on page
Parameter configuration
The transmitter can be adapted to fit perfectly into any application by adjusting the software parameters. The parameters
are set with the operation terminals OPA-S or the optional bult-in OPC-S. The OPA-S may also be used as remote
indicator.
NOTE: For the correct display of data, version 1.7 or grater of OPA-S is required.
OPA-S operation
1.
Open SDC housing (see SDC-C1 installation sheet no. 70-00-0573
http://www.vectorcontrols.com/
2.
Connect the OPA-S operating device to the OPA-S connector on the SDC (see section
” on
page 3). The measured CO2 value is displayed.
3.
Press the "Up" and "Down" keys simultaneously for more than 3 seconds. "Code 0000" is displayed.
4.
Use the "UP" and "DOWN" keys to set the password "0009" and confirm with the "RIGHT" key.
5.
Select "IP SEL
(Input Parameter) or “OP SEL” (Output Parameter) with
"UP" and "DOWN" and confirm with the
"RIGHT" key. The first parameter is displayed.
6.
Use the "UP" and "DOWN" key to switch to the desired parameter. After pressing the "RIGHT" key adjust the
parameter value with the "UP" and "DOWN" keys. Confirm the setting with the "RIGHT" key.
7.
Complete parameter setting by pressing the left "ON/OFF" key twice. The measured CO2 value is displayed.
Important
In order for the SDC-C1 to apply the new settings correctly, the parameter setting must be completed with the
left "ON/OFF" key!
Detailed information on the OPA-S can be found on the website
product page under "Downloads".
OPC-S operation
1.
Press the "Up" and "Down" keys simultaneously for more than 3 seconds. "Code 0000" is displayed.
2.
Use the "UP" and "DOWN" keys to set the password "0009" and confirm with the "RIGHT" key.
3.
Select "IP SEL
(Input Parameter) or “OP SEL” (Output Parameter) with
"UP" and "DOWN" and confirm with the
"RIGHT" key. The first parameter is displayed.
4.
Use the "UP" and "DOWN" key to switch to the desired parameter. After pressing the "RIGHT" key adjust the
parameter value with the "UP" and "DOWN" keys. Confirm the setting with the "RIGHT" key.
5.
Complete parameter setting by pressing the left "ON/OFF" key twice. The measured CO2 value is displayed.
Important
In order for the SDC-C1 to apply the new settings correctly, the parameter setting must be completed with the
left "ON/OFF" key!
Detailed information on the OPC-S can be found on the website
product page under "Downloads".
Signal type
JP1
Voltage (VDC)
Current (mA)
Signal range
JP4
0
…
10 V, 0
…
20 mA
2
…
10 V, 4
…
20 mA