background image

Installation

IT IS  IMPORTANT  THESE  INSTRUCTIONS  ARE

READ FULLY BEFORE INSTALLATION

This product should not be used for any purpose other

than that for which it was designed and as shown

in this leaflet

All packaging should be removed and the unit checked

for damage in transit.  If there is any damage, please 

contact your supplier

• The WHHRMaxi-C/Maxi Plus must be installed verti-

cally, and generally be fitted into a cupboard, loft or 

ceiling void.  

In order to comply with Construction (Design & Man-

agement) Regulations, sufficient access for safe 

maintenance (recommended on an annual basis),  or

removal following installation, MUST be provided for

this product.    We recommend that a clearance of 

at least 150mm is available on each side of the cab-

inet to allow access to the motors.  See dimensions

diagram.

Regulations and current Building Regulations.  In order to comply with these, it may be necessary to fit fire 

dampers or other similar devices within the associated ductwork.

• Flue gases from fuel-burning equipment must not  be drawn into a living area.  If any room from which air

is extracted contains a fuel burning appliance, such as a central heating boiler, then its flue must be of the

sealed or balanced flue type, or allowance must be made for an adequate supply of air into the room.

The unit must

NOT

be installed:

- where there is excessive oil or grease

- where there are hazardous gasses, liquids or vapours that are flammable or corrosive

- in ambient temperatures above 40ºC or lower than 0ºC

- in areas of excessive humidity or in a wet environment

• Where possible the unit should 

NO

T be installed directly above a bedroom or living room.  

The condensation drain 

MUST

be fitted

Care should be taken to ensure that ducting is free from blockages

External grilles should be located a minimum of 600mm from any flue outlet in accordance with all Regulations

The unit must be connected to a 230-240v, 50Hz single phase electrical supply.  

•    A triple pole isolation switch with contact  separation of at least 3mm must be used to connect the appliance

     to the fixed wiring when using the Switched Live. 

    The product should only be connected to the mains electricity supply or electrical outlet if:

     -    your electrical voltage and frequency correspond to those shown on the rating label.

     -    the capacity of your electricity supply is sufficiently powerful to operate the product at its maximum power.

    If one of the spigots is not connected to ducting a safety grille 

MUST 

be fitted to that spigot, so that it is 

     impossible for any moving part to be touched.

Installation of the appliance 

MUST

be carried out by a qualified and suitably competent person and should be 

carried out in clean, dry conditions where dust and humidity are at minimal levels. The unit is not suitable for 

installation to the exterior of the dwelling.

Transportation, packaging and storage prior to 

installation

•    Care should be taken when transporting the unit.  

     Please be aware that this unit weighs 36 Kg - we 

     recommend the use of appropriate handling and lift-

     ing equipment.  Dropping or knocking will damage the

     inner workings of the unit.

•    The unit should always be stored in a clean, dry 

     environment.

•    Remove all packaging before installation.

Pre-inspection

•    Inspect the unit and electrical supply cord for any 

     damage (damage must be repaired by a suitably 

     qualified and competent person.)

•    Check all parts are supplied as shown.

Page 3

Reviews: