"EVO220" - WHOLE HOUSE HEAT RECOVERY UNIT
INSTALLATION AND OPERATING INSTRUCTIONS
Safety Notice
It is important to read this Instruction Manual carefully before installing or using the product. Following these instruc-
tions will ensure that your ventilation system is installed, commissioned and used properly and continues to operate ef-
fectively. Vectaire will not be held responsible and will not accept liability for any damage caused to persons or property
through failure to follow the guidance provided in this manual. It should always be available with the product for easy
reference.
EVO220 -
5"/125mm spigot, max capacity 75 l/sec
-
General Information
The Vectaire EVO220 heat recovery system provides whole house mechanical
ventilation to living areas, bedrooms, kitchen and bathrooms. It extracts stale,
contaminated air from kitchens, utility rooms and bathrooms, and uses the heat
recovered from this air to warm fresh, incoming air to create a flow of fresh
air throughout the dwelling. The extract and intake air streams are separated
to avoid contamination.
The system will operate continuously to create a stable, comfortable, healthy
environment avoiding the use of excessive energy and saving heat already gen-
erated.
The heat recovery unit will generally be installed in the loft of a house or the void
above the ceiling in an apartment (but may be installed in a cupboard) and will
be connected by hidden ductwork to vents sited in the ceilings of the rooms
which require ventilation. Each unit is commissioned individually allowing its per-
formance to be tailored to suit the performance required. There will be a facility
to boost the extraction rate when desired (e.g when cooking or bathing or pol-
lutant levels rise). This may be done automatically or manually.
The system is designed to run continuously and should NOT be switched off
except for maintenance or filter replacement. It is important to follow the
advice in this user manual and correctly install and maintain the system to ensure a healthy and comfortable indoor
environment.
Features
•
whole house heat recovery units giving continuous ventilation in the kitchen and up to five additional wet rooms
•
low noise levels
•
variable choice low (trickle) speed and boost options for optimum setting at installation
•
boost speed can be triggered by a switched live connection from a variety of external devices including:
- PIRFF (passive infra red)
*
- DRH240 (dynamic remote humidistat)
*
- THM (thermostat)
*
- a light switch (if more than one light switch is used,
each one must be a double pole switch)
- a remote switch/pull cord
or via LCD control panel
• Economical EC motor with electronic control plus:
Standard control features
> Independent motor speed control
•
Each motor can be adjusted independently
•
Trickle, boost and purge speeds can be set at installation
> Adjustable over-run timer -
from 0-90 Minutes, factory set to 0 minutes
> Adjustable delay-on timer -
from 0-5 Minutes, factory set to 2 minutes
> Integral frost stat –
proportionally reduces intake motor speed as temperature falls
> BMS connections
– for remote motor shut off
•
Installation MUST be carried out by suitably qualified personnel and MUST be in accordance with current IEE
regulations