IT IS IMPORTANT THESE THESE INSTRUCTIONS ARE READ FULLY
BEFORE INSTALLATION
•
This product should not be used for any purpose other than that for
which it was designed and as shown in this leaflet.
•
All packaging should be removed and the unit checked for damage
in transit. If there is any damage, please contact your supplier.
• The EVO220 will generally be fitted into a loft or ceiling void.
In order
to comply with Construction (Design & Management) Regula-
tions, sufficient access for safe maintenance (recommended on
an annual basis), or removal following installation, MUST be pro-
vided for this product. See dimensions.
•
Fire Dampers
must be fitted
to duct work at appropriate locations
in accordance with Building Regulations
• Flue gases from fuel-burning equipment must not be drawn into
a living area. If any room from which air is extracted contains a
fuel burning appliance, such as a central heating boiler, then its
flue must be of the sealed or balanced flue type, or allowance
must be made for an adequate supply of air into the room.
•
The unit must NOT be be installed:
- where there is excessive oil or grease
- where there are hazardous gases, liquids or vapours that are flammable or corrosive
- in ambient temperatures above 50ºC or lower than 5ºC (-28ºC using pre-heater)
- in humidity levels above 90% or in a wet environment
• Where possible the unit should NOT be installed directly above a bedroom or living room.
•
The condensation drain
must
be fitted and if insulated, use the equivalent of at least 25mm of insulating material with a
thermal conductivity of 0.04 W/(mK)
•
Care should be taken to ensure that ducting is free from blockages before switching on the unit as this may invalidate
your guarantee
•
External grilles should be located a minimum of 600mm from any flue outlet in accordance with all Regulations
•
The unit must be connected to a 230v-240v, 50Hz single phase electrical supply.
•
A triple pole isolation switch with contact separation of at least 3mm must be used to connect the appliance to the
fixed wiring when using the Switched Live.
•
The product should only be connected to the mains electricity supply or electrical outlet if:
- your electrical voltage and frequency correspond to those shown on the rating label.
- the capacity of your electricity supply is sufficiently powerful to operate the product at its maximum power.
•
If one of the spigots is not connected to ducting a safety grille
MUST
be fitted to that spigot, so that it is impossible for any
moving part to be touched.
Installation of the appliance
MUST
be carried out by a qualified and suitably competent person and should be
carried out in clean, dry conditions where dust and humidity are at minimal levels. The unit is not suitable for
installation to the exterior of the dwelling.
Page 3
Handing - Bottom Access Left
Handing - Bottom Access Right
Handing - Top Access Left
Handing - Top Access Right
Dimensions
N.B
a clearance of at least 200 mm should be allowed
on each side of the cabinet for access to the interior