Series 655
INSTALLATION
979645EA
Edition 23.09.2019
65/112
4.10.6
Connection Object (Class ID 5)
Manage the characteristics of a communication connection
Command
Service Code
Class ID
Instance ID
Attribute ID
Service
data length
(number of bytes)
Service
data field
Description
POLL OUTPUT
Set
16
5
2
100
1
X
Get
14
X:
output assembly object number (7,8,102)
Contains the instance number of the assembly used by the poll connection to send data.
(data from host to valve)
POLL INPUT
Set
16
5
2
101
1
X
Get
14
X:
input assembly object number (3,4,5,13,14,100,101)
Contains the instance number of the assembly used by the poll connection to receive data.
(data from valve to host)
BIT STROBE INPUT
Not implemented
CHANGE OF STATE
CYCLING INPUT
Set
16
5
4
101
1
X
Get
14
X:
input assembly object number (3,4,5,13,14,100,101)
Contains the instance number of the assembly used by the poll connection to receive data.
(data from valve to host)
4.10.7
Discrete Input Object (Class ID 8)
Defines the interface to the open/close limit switches
Command
Service Code
Class ID
Instance ID
Attribute ID
Service
data length
(number of bytes)
Service
data field
Description
VALVE
CLOSED CHECK
Get
14
8
1
3
1
X
This command returns:
X:
0
valve is not closed
1
valve is closed
VALVE
OPEN CHECK
Get
14
8
2
3
1
X
This command returns:
X:
0
valve is not open
1
valve is open