81
12.4.5.2
Manual entry
•
Select
Manual entry in the drop-down list.
You can set the target value for cos(phi) between 0.9
under-excited and 0.9 over-excited. To this end, select the
desired value in the drop-down list.
Target value for cos(phi) Power factor set value
Under-excited
0.90
-100
0.91
-90
0.92
-80
0.93
-70
0.94
-60
0.95
-50
0.96
-40
0.97
-30
0.98
-20
0.99
-10
1.00
0
Over-excited
0.99
10
0.98
20
0.97
30
0.96
40
0.95
50
0.94
60
0.93
70
0.92
80
0.91
90
0.90
100
Time delay:
Enter the time in seconds after which the idle power is to be reset.
Minimum power:
Enter the minimum power up to which the idle current is not regulated in per cent (%).