39
11.2
Setup site requirements
Danger
Blocked escape routes
Possible danger to life and material damage.
Keep escape routes clear.
Do not mount the energy store in areas that block escape routes.
Do not lay or deposit objects in areas of the escape routes.
Avoid tripping hazards.
WARNING
Entry of water into electrical installations.
Danger to life due to electric shock.
Set up the storage cabinet only within buildings.
Pay attention to the IP protection class of the energy store
Comply with all the requirements concerning the setup site.
CAUTION
Personal and material damage due to erroneous setup and lack of space.
Crushing injuries to limbs.
Position the cabinet in such a way that hazard-free installation, operation,
maintenance and dismount is possible in the case of intended use.
11.3
Suitable assembly sites
Suitable sites include dry cellars, service entrance rooms and utility rooms.
At assembly, be aware that operating noises of the energy store may be disruptive.
11.4
Setup site
The following measurements and general conditions must be complied with at the setup site.
11.4.1
Dimensions and equipment
For the room in which VARTA element backup is set up, a
volume of at least 30 m
³
is recommended. A horizontal, flat
floor with a minimum surface area of 70 cm x 55 cm
(width x depth). The floor must be sufficiently stable.
For the weight of the energy store, see chapter 3.8 “Technical
parameters”, beginning on page 20.
•
If appropriate, have the statics checked.
The subsurface, connecting walls and ceilings must not
consist of heart-sensitive materials.
•
A smoke detector must be installed in the setup room of the VARTA element backup.