background image

9

Värmebaronen EK 13

Troubleshooting

Intervention that requires tools must be performed by a qualified electrician.

Fault

Possible cause of fault

Action

Operating indicators off.

Electric cartridge without 
power.

Check the main fuses.

Main switch off.

Turn the switch to position I. The time delay function will lock the power 
stages if it has been without power for more than three minutes.

The electric cartridge is 
blocked by external equipment.

Check whether the electric cartridge is blocked by external control or 
similar.

Overheating protection 
triggered.

If the overheating protection has been triggered, the operation of the 
system's circulation pumps and valves must be checked.
Reset by pressing the overheating protection button. This may take place 
when the temperature has fallen below 80 °C.

Connection is limited by 
a power cut.

It is possible to bypass the time delay function on the printed circuit board.

Load guard limits power 
stages.

Check whether the load guard is connected and whether it is limiting the 
power stages.

Operating indicator for 
stage one off. Stage two 
and/or stage three on.

Miniature circuit breaker in 
automatic control cabinet 
triggered.

Check where the short-circuit is. Take action. Then reset the miniature 
circuit breaker.

Operating indicators for 
stages two and three off. 
Stage one on.

Miniature circuit breaker on 
circuit board triggered.

Check where the short-circuit is. Take action. Then reset the miniature 
circuit breaker.

Group fuses for electric 
cartridge triggered.

Immersion heater faulty.

Switch off the main switch. Check the insulation of the immersion heater's 
power groups. If any of the electric elements is faulty, replace the immersion 
heater and the tank for the immersion heater.

The operation of the 
electric cartridge is 
irregular. The thermostats 
are switching on and off 
at regular intervals.

Water flow too low.

Check that the circulation pumps are working and that all necessary valves 
are open.
The flow through the electric cartridge is checked as follows:
a.  Limit the power stages of the electric cartridge so that the power output

is constant, for example to 1 power stage.

b.  Let the temperature of the electric cartridge become stabilised and

measure the temperature increase between the flow and return lines of
the electric cartridge.

c.  Calculate the water flow using the formula below.

Recommended flow: 0.3 litre/second, 

t = 10 °C.

q = 

P

t x 1.16

q = water flow in m3/h
P = cartridge's power output in kW.

t = temperature difference in °C.

1.16 = water's thermal absorption coefficient.
To obtain the flow in litre/second, multiply q by 1/3.6

Summary of Contents for EK 13

Page 1: ...2 1 1 2 2 0 1 1 Installation and maintenance Electric cartridge EK 13...

Page 2: ...External blocking Connection delay after power cut Limitation of power Load guard Electrical installation wiring diagram 7 Control panel 8 Operation and maintenance 8 General Operation Overheating pro...

Page 3: ...3 V rmebaronen EK 13 Tel Notes Production number Installation date Installer Other To be completed when the cartridge is installed...

Page 4: ...n free The system must be leakproof so that the water does not need to be replaced with new oxygen rich water and the water is not oxygenated during installation Water quality in respect of suitable t...

Page 5: ...oxygenation of the heating system Closed system The cartridge is connected to a closed expansion tank and in an unbroken uninterruptible connection to a type approved safety valve with maximum 3 bar...

Page 6: ...rating mode and open in idle mode 25 4 1 To external control unit Connection delay after power cut The electric cartridge has connection delayed power stages after a power cut according to the standar...

Page 7: ...ower group three 3 kW 15 Indicator power stage two 16 Indicator power stage three 17 Thermostat power stages two and three 18 Printed circuit board 19 Relay group power stage two 20 Relay group power...

Page 8: ...Otherwise it works in the same way as the thermostat for power stage one Overheating protection The electric cartridge has overheating protection that is triggered when the temperature exceeds approxi...

Page 9: ...circuit is Take action Then reset the miniature circuit breaker Operating indicators for stages two and three off Stage one on Miniature circuit breaker on circuit board triggered Check where the sho...

Page 10: ...e EK 13 1 1 160003 12 pole terminal block 1 160006 End plate 1 160009 2 pole bridge 2 160011 4 pole bridge 1 9 170046 Contactor 230 V 1 7 180021 Miniature circuit breaker 10 A 1 11 15 16 190002 Indica...

Page 11: ......

Page 12: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 Fax 46 44 22 63 58 www varmebaronen se www varmebaronen com info varmebaronen se...

Reviews: