Värmebaronen EK 13

552

340

585

310

Technical data

Alternative bracket location

General

The ambient temperature must not exceed 30 °C.
Cables and pipes must be laid so that it is possible to remove 
the front plate and open the roof plate for service. For installa-
tion and accessibility for service, there must be at least 60 cm 
space above and in front of the cartridge.
The electric cartridge is not designed for oxygenated water.
No work must take place on the electric cartridge's facing 
plates.

Water quality

Tap water is usually classified from the point of view of hygiene. 
Good water classified on this basis is not automatically suitable 
for a heating system. To avoid problems a technical water analysis 
should take place. Any nonconformities with standard values 
should be corrected.
If the volume of the heating system is low, it can be filled with 
water that was not classified as good system water. When the 
water is heated, some oxygen and carbonic acid are emitted to the 
expansion tank or vent valves. The remainder will react with the 
metals in the system. This corrosion is often insignificant as the 
same volume of water circulates and it soon becomes oxygen-free.

The system must be leakproof so that the water does not need 
to be replaced with new oxygen-rich water and the water is not 
oxygenated during installation.

Water quality, in respect of suitable tap water:
The alkalinity should exceed 60 mg/l to avoid corrosion.
Contents of carbonic acid over 25 mg/l increase the risk of 
corrosion.
Sulphate contents over 100 mg/l may accelerate corrosion. 
If the sulphate content is higher than the alkalinity, there is 
a risk of copper corrosion.
Hard water causes boiler scale and is not suitable in a heating 
system.
Very soft water may cause corrosion damage.
Chloride contents over 100 mg/l make the water aggressive, 
in particular with lime deposits.
Low pH values may cause corrosion damage. The pH value 
should be 7.5-8.5.
The incidence of carbonic acid in combination with low pH 
and hardness values makes the water aggressive.

1.  Terminal block.
8.  Overheating protection.
9. Contactor.
18. Printed circuit board.
28. Flow line R25 ext.
29. Return line R 25 ext.
30. Cover over mounting plate.
31. Mounting plate.
32. Cable opening.
33. Wall bracket.

8

28

29

30

1

9

18

8

31

32

33

Weight:

13 kg

Design temperature:

110 °C

Current:

18.8 A

Volume:

3.6 litre

Operating temperature:

30-85 °C

Fuse:

3 x 20 A

Design pressure:

3 bar

Power:

13 kW

Enclosure protection class:

IP 21

Test pressure:

4.3 bar

Voltage:

400V 3N~, 50 Hz

Manufactured to 

PED 97/23/EC article 3.3

Summary of Contents for EK 13

Page 1: ...2 1 1 2 2 0 1 1 Installation and maintenance Electric cartridge EK 13...

Page 2: ...External blocking Connection delay after power cut Limitation of power Load guard Electrical installation wiring diagram 7 Control panel 8 Operation and maintenance 8 General Operation Overheating pro...

Page 3: ...3 V rmebaronen EK 13 Tel Notes Production number Installation date Installer Other To be completed when the cartridge is installed...

Page 4: ...n free The system must be leakproof so that the water does not need to be replaced with new oxygen rich water and the water is not oxygenated during installation Water quality in respect of suitable t...

Page 5: ...oxygenation of the heating system Closed system The cartridge is connected to a closed expansion tank and in an unbroken uninterruptible connection to a type approved safety valve with maximum 3 bar...

Page 6: ...rating mode and open in idle mode 25 4 1 To external control unit Connection delay after power cut The electric cartridge has connection delayed power stages after a power cut according to the standar...

Page 7: ...ower group three 3 kW 15 Indicator power stage two 16 Indicator power stage three 17 Thermostat power stages two and three 18 Printed circuit board 19 Relay group power stage two 20 Relay group power...

Page 8: ...Otherwise it works in the same way as the thermostat for power stage one Overheating protection The electric cartridge has overheating protection that is triggered when the temperature exceeds approxi...

Page 9: ...circuit is Take action Then reset the miniature circuit breaker Operating indicators for stages two and three off Stage one on Miniature circuit breaker on circuit board triggered Check where the sho...

Page 10: ...e EK 13 1 1 160003 12 pole terminal block 1 160006 End plate 1 160009 2 pole bridge 2 160011 4 pole bridge 1 9 170046 Contactor 230 V 1 7 180021 Miniature circuit breaker 10 A 1 11 15 16 190002 Indica...

Page 11: ......

Page 12: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 Fax 46 44 22 63 58 www varmebaronen se www varmebaronen com info varmebaronen se...

Reviews: