Page 8
CPS-2M
Once the CPS-2M is in place, use a screwdriver to remove
the six screws holding the faceplate to the housing.
2.3 SWITCH SETTING
The CPS-2M is configured for a variety of options via two
switches: the line voltage selector switch, and the software
settings DIP switch. These switches are described in the
following two sections.
2.3.1 - Line Voltage Selector Switch
This switch is located on the surface of the main (bottom)
board and adapts the CPS-2M for 115 VAC or 230 VAC
line voltage. The manufacturer set the switch to 230 VAC.
If you wish to use it on 115 VAC you have to select to 115
VAC before turning on the power
Refer to figures 1 through 2.
2.3.2 - Software Settings DIP Switch
This switch is located at the rear of the CPS-2M faceplate
and adjusts the following options.
1
2
3
4
Switch 1
Fahrenheit or Celsius display on the CPS-
2M
Switch 2
Locks or unlocks your settings. All settings
except for main set point, record low, and
record high are locked while this switch is
off.
Switch 3
Increases static pressure sensitivity with DIP
switch set to OFF. (The static pressure
reading will react faster with High
sensitivity).
Switch 4
Static pressure mode or temperature mode.
230V
115V
OFF
ON
Fahrenheit
Settings locked
High static pressure sensitivity
Temperature mode
Celsius
Setting unlocked
Normal static pressure sensitivity
Pressure mode
OFF ON