CPS-2M
STAGE 1 LOW TEMPERATURE / PRESSURE
ALARM
This function establishes the temperature /
pressure
difference
below the main set point
that the room can reach before a low
temperature alarm is signalled. When a low
temperature / pressure alarm occurs the alarm
relay is activated and the alarm LED lights on
the CPS-2M.
When a temperature probe is installed the low
temperature alarm is adjusted in 0.5 degree
increments from a minimum setting of -30.0°F
(-18.0°C) to a maximum setting of 0.0°F (0.0°C)
When a pressure probe is installed the low
pressure alarm is adjusted in 0.01" H
2
O
increments from a minimum setting of -0.10"
H
2
O to a maximum setting of 0.00 " H
2
O.
Adjusting the low temperature / pressure
alarm setting:
•
rotate the Selector dial to position (12),
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode,
•
rotate the Selector dial to position (7),
•
rotate the Adjustor dial counterclockwise to
decrease the setting, and clockwise to
increase it.
The low temperature alarm setting is displayed
on the CPS-2M.
Alarm