CPS-2M
STAGE 2 MAIN SET POINT
TEMPERATURE / PRESSURE
When a temperature probe is installed, the
main set point establishes the target
temperature in the building. The main set point
temperature is adjusted in 0.5 degree
increments from a minimum setting of 42.0°F
(5.5°C) to a maximum setting of 111°F (44.0°
C).
When a static pressure probe is installed, the
main set point establishes the target pressure
level in the building. The main set point
pressure level is adjusted in 0.01" H
2
O
increments from a minimum setting of OPN,
0.0" H
2
O to a maximum setting of 0.14" H
2
O,
and CLO.
Adjusting the main set point temperature /
pressure level:
•
rotate the Selector dial to position (2),
•
rotate the Adjustor dial counterclockwise to
decrease the setting, and clockwise to
increase it.
The main set point temperature / pressure level
is displayed on the CPS-2M.
Note:
The actuator motor may be manually controlled by
adjusting the main set point to OPN or CLO thereby
causing the air inlet to either remain fully open or
closed.