CT-6500 Series 2 Operating Instructions
15
6.0 CT-6500 Analyzer Specifications
PHYSICAL SPECIFICATIONS
16” W by 11”H by 14”D (40.6 cm x 29.9 cm x 35.6 cm)
Weight: 25lbs (11.3Kg).
INPUT POWER
8 Amperes, 90-120Vac or 200-240Vac (selectable), 50/60 Hz.
DRY-CONTACT INPUT
3 or 6 or 12 contact channels. All contact inputs are grounded until testing
is started. Each contact detects main and insertion resistor contacts.
TIMING WINDOW
Selectable between: 1, 10, or 20 second.
TIMING RESOLUTION
±50 microseconds at 1 second duration.
±0.5 millisecond at 10 second duration.
±1.0 millisecond at 20 second duration.
TIMING ACCURACY
0.05% of reading,
?
50 micro-seconds at 1-second duration.
CONTACT DETECTION RANGE
CLOSED: less than 20 Ohms.
RANGE
OPEN: greater than 10,000 Ohms.
RESISTOR DETECTION RANGE
Ranges from 10 to 7,000 Ohms.
EXTERNAL TRIGGER INPUT
Open/Close: 30 to 300Vdc, peak Vac.
VOLTAGE SENSING INPUTS
V1: analog input, 0-255V dc or peak ac. Sensitivity:
?
1V;
V2: voltage detector (present/absent).Input: 30-300V, dc or peak ac.
BREAKER OPERATION
Open, Close, Open-Close, Close-Open, and Open-Close-Open.
BREAKER INITIATE CAPACITY
30A/250V ac/dc max (100A inrush).
INITIATE CURRENT READING
One, Non-contact, hall-effect sensor ranging from 0-20 Amperes, DC to 5 kHz.
RANGE
TRAVEL TRANSDUCER
3 travel-transducer channels. Linear motion from 0.0 to 30.0 inches (±0.01) inch.
INPUT
Rotary ranges from 0 to 360
o
(± 0.36º).
BREAKER SLOW-CLOSE
Measures “Slow-Close” the contact point distance (hard copy printout).
TEST
DISPLAY
Back-lit LCD screen, 4-lines by 20-characters, sunlight viewable.
PRINTOUT
Both graphic contact-travel waveforms & tabulated results are printed on 4.5 inch
thermal paper.
STORAGE CAPABILITIES
Store up to 100 timing records.
COMPUTER INTERFACE
RS-232C Port, USB Port.
PC SOFTWARE (included)
Furnished Circuit Breaker Analyzer PC software. Windows XP and Windows Vista
compatible. The analysis software can be installed on an IBM-compatible computer
for graphical display, numerical reports and database utility for office use.
SAFETY
Designed to meet UL 61010A-1 Certification and CAN/CSA C22.2 No 1010.1-92.
Summary of Contents for CT-6500 2 Series
Page 22: ...CT 6500 Series 2 Operating Instructions 21 Figure 4 0 Series Contact Cable Connection...
Page 77: ...CT 6500 Series 2 Operating Instructions 76 APPENDIX F SIEMENS TCP Breaker Velocity Calculation...
Page 79: ...CT 6500 Series 2 Operating Instructions 78 APPENDIX H CT 6500 SIEMENS SPS2 Test Plan...
Page 82: ...www vanguard instruments com...