9.4 Supporting functions
9 Technical data
Technical description
174
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
9.3.5.
Digital input / output card (option)
Number of digital inputs
4 (5)
External operating voltage
Voltage selectable in order code (same as DI
threshold voltage for the relay):
A: 24 V dc / 110 V ac
B: 110 V dc / 220 V ac
C: 220 V dc
Operating voltage level
12 V dc
Current drain, when active
Approx. 2 mA
Number of digital outputs
(1)
Rated voltage
Continuous carry
Make and carry 0.5 s
Make and carry 3 s
250 V dc / ac
5 A
30 A
15 A
Breaking capacity. DC ( L/R = 40 ms)
at 48 V dc:
at 110 V dc:
at 220 V dc:
1.0 A
0.44 A
0.22 A
Terminal block
Phoenix MVSTBW or equivalent
Maximum wire dimension:
2.5 mm2 (13 – 14 awg)
NOTE! Approximately 2 mA of current is going trough the T5 (X6:1 & X6:2) circuit
even when used as a digital output. This has to be noticed when T5 is
used with certain type of applications (if 2 mA is enough to control for
example a breaker).
When DI/DO-option cards are ordered separately the threshold has to be
modified manually on field according the description in the manual (See
chapter 8.6).
9.4.
Supporting functions
9.4.1.
Disturbance recorder (DR)
The operation of disturbance recorder depends on the following
settings. The recording time and the number of records depend
on the time setting and the number of selected channels.
Disturbance recorder (DR)
Mode of recording:
Saturated / Overflow
Sample rate:
- Waveform recording
- Trend curve recording
32/cycle, 16/cycle, 8/cycle
10, 20, 200 ms
1, 5, 10, 15, 30 s
1 min
Recording time (one record)
0.1 s – 12 000 min
(must be shorter than MAX time)
Pre-trigger rate
0 – 100%
Number of selected channels
0 – 12