3.13 Combined overcurrent status
3 Supporting functions
Technical description
176
VAMP 24h support phone +358 (0)20 753 3264
VM259.EN007
Parameter
Value
Unit
Description
Note
LINE FAULT
Flt
L1
Flt
L2
Flt
L3
0
1
Fault (=trip) status for each
phase.
0=No fault since fault ClrDly
1=Fault is on
OCt
0
1
Combined overcurrent trip
status.
Flt
L1
=Flt
L2
=Flt
L3
=0
Flt
L1
=1 orFlt
L2
=1 or Flt
L3
=1
LxTrip
On
Off
'On' Event enabling for
Flt
L1
...3
Events are enabled
Events are disabled
Set
LxTripOff
On
Off
'Off' Event enabling for
Flt
L1
...3
Events are enabled
Events are disabled
Set
OCTrip
On
Off
'On' Event enabling for
combined o/c trips
Events are enabled
Events are disabled
Set
OCTripOff
On
Off
'Off' Event enabling for
combined o/c starts
Events are enabled
Events are disabled
Set
IncFltEvnt
On
Off
Disabling several events of
the same fault
Several events are enabled
*)
Several events of an
increasing fault is disabled
**)
Set
ClrDly
0 ...
65535
s
Duration for active alarm
status Flt
L1
, Flt2, Flt
L3
and
OCt
Set
Set = An editable parameter (password needed)
*) Used with IEC 60870-105-103 communication protocol. The alarm screen
will show the latest if it's the biggest registered fault current, too. Not used
with Spabus, because Spabus masters usually don't like to have unpaired
On/Off events.
**) Used with SPA-bus protocol, because most SPA-bus masters do need an
off-event for each corresponding on-event.