 INSTALLATION GUIDE 

BL-Series

Summary of Contents for BL120

Page 1: ...Version 2018 1 www valoya com 358 10 2350 300 BL Series INSTALLATION GUIDE BL Series...

Page 2: ...Una instalaci n inadecuada puede provocar lesiones o da ar la l mpara ATENCION No seguir atentamente las instrucciones es peligroso y puede causar una descarga el ctrica Si la manguera flexible exteri...

Page 3: ...d elanslutning 3 Minsta avst nd till belyst f rem l 4 Endast f r inomhusbruk Arbetstemperatur 5 ndra eller l sg r inte n gon del av arma turen Valoya 1 2 3 4 5 SUOMI HUOMIO Valaisimen huolimaton asenn...

Page 4: ...29 Annex E No AC mains plug fitted No Physical Length mm in 1176 46 3 Width mm in 73 5 2 9 Height mm in 58 2 3 Weight kg lb 3 2 7 1 Cable length each end of luminaire mm in 300 11 8 Minimum distance f...

Page 5: ...ective compliant X Low Voltage Directive compliant X Eco design EuP directive compliant X Certified to UL CSA standards No Warranty 3 year limited warranty please refer to our terms conditions for mor...

Page 6: ...the carrier about the damage immediately Ask the carrier to write down a statement that the delivery was not delivered in good condition If the packaging shows no damage but the goods inside are defec...

Page 7: ...Version 2018 1 www valoya com 358 10 2350 300 Installation Instructions 7...

Page 8: ...require one 1 Wieland RST female mating connector to enable connection of a mains input cable and one 1 blank end cap to protect and seal the last connector of the chain These additional components ar...

Page 9: ...ion Installation Instructions IMPORTANT Maximum 16 luminaires to be connected to one 16A Type C MCB Higher rated MCB use is not permitted Use of an incorrectly rated MCB will cause a potential safety...

Page 10: ...ty on a 16A Type C MCB BX series BX90 BX120 BX180 6 BL series BL120 16 C series C65 C75 C90 6 R series R300 3 LightDNA 8 LightDNA 8 2 ICL INRUSH CURRENT LIMITER An ICL can help avoid nuisance MCB trip...

Page 11: ...to protect against surge peaks above 4KV e g due to a lightning strike we recommend the installation of transient voltage surge suppression Do not apply power without the Neutral connected Ensure the...

Page 12: ...and disconnect the luminaire unplug the Wieland input connector Connect the luminaire to a mains supply circuit known to be providing voltage If the problem remains then the luminaire may be damaged...

Page 13: ...e following information about the issue Product model information e g B200 NS1 Product serial number plus YF or XF code Quantity showing problems Detailed problem description Photograph or video showi...

Page 14: ...ectromagnetic compatibility EMC Part 4 6 Testing and measurement techniques Immunity to conducted disturbances induced by radio frequency fields IEC EN 61000 4 8 Electromagnetic compatibility EMC Part...