Valor Ultimate Installer'S Manual Download Page 29

15.2 Flame Supervision & Spillage Monitoring System

The pilot unit incorporates a system that will automatically shut off the gas supply if the
pilot flame goes out or if there is insufficient oxygen due to spillage or lack of
ventilation.
Check that the system operates properly as follows;

Light the appliance. Set at the “HIGH” position and leave for one minute.

Turn back to “OFF” to extinguish the pilot. 

Note the time when the pilot goes out.

Listen for a snap sound at the gas tap. 

Note the time when the sound is heard. 

This

sound is caused by an electromagnetic valve shutting off the gas supply through the tap.
The valve is located in the body of the tap. The valve should operate 

within 60 seconds

of the pilot going out.

If the valve does not operate within this time limit do not allow

the appliance to be used until the fault has been corrected.

This monitoring system must not be adjusted, bypassed or put out of operation.
This monitoring system, or any of its parts, must only be exchanged using Valor
authorised parts.

16. FINAL REVIEW

1.

Visually inspect the appliance. Clean off any marks incurred during installation.

2.

Advise the customer how to operate the fire.

3.

Explain to the customer that the appliance has a flame failure and spillage monitoring

system. Point out the explanation of this system shown in the owner’s guide.
Advise that if the fire goes out for any reason, wait at least three minutes before
relighting. Stress that if the monitoring system repeatedly shuts off the fire, the
appliance should be switched off and a specialist should be consulted. Point out that the
lighting instruction details are on a metal plate attached at the bottom of the appliance.

4.

Advise that the fire may give off a slight odour while new.  This is quite normal and

it will disappear after a short period of use.

5.

Advise that any cleaning must only be carried out when the fire is off and cold.

6.

Advise the customer that they should read the Owner’s guide before operating the fire

and always follow the advice in the section headed “Cleaning your fire”.

7.

Advise the customer that the appliance will operate to its maximum potential if the

flue is primed during the first 20 – 30 minutes of use. To do this, simply turn the control
to its highest setting. This will also burn off any carbon deposits that may have formed
during previous use.
If using the appliance for long periods it is beneficial to change between settings. This
will also help to remove any carbon deposits that may form during use.

Page 29

INSTALLER GUIDE

Summary of Contents for Ultimate

Page 1: ...National call rates apply in the United Kingdom In the Republic of Ireland call 0044 08706 061 065 INSTALLER Please leave this guide with the owner Valor Heating Ultimate Model 717 GC No 32 032 52 INS...

Page 2: ...a member of the Society of British Gas Industries which works to ensure high standards of safety quality and performance Careful Installation Valor is a CORGI registered company All our gas fires must...

Page 3: ...hecks 22 10 2 1 Lighting the burner 22 10 2 2 Operating the burner 22 10 3 Reference Pressure Check 23 11 FITTING THE FRONT SURROUND 23 12 CERAMIC COALS INSTALLATION 24 13 FIREFRONT CASTING8INSTALLATI...

Page 4: ...ance When lifting always keep your back straight Bend your legs and not your back Avoid twisting at the waist It is better to reposition your feet Avoid upper body top heavy bending Do not lean forwar...

Page 5: ...or the disposal of industrial waste Protective clothing is not required when handling these articles but we recommend you follow the normal hygiene rules of not smoking eating or drinking in the work...

Page 6: ...the following British Standards BS 715 BS 1251 BS 1289 Part 1 BS EN 1806 BS 4543 Part 2 BS 5440 Part 1 BS 5440 Part 2 BS 5871 Part 1 BS 6461 Part 1 BS 6891 In England and Wales the current edition of...

Page 7: ...nce from the base of the fireplace opening in the wall to the finished floor level is at least 72mm 3 2 2 To a fireplace incorporating a metal flue box conforming to BS715 with a minimum internal dept...

Page 8: ...ng This may cause cracking of the surround back or marble 3 3 The following flues are suitable 225mm x 225mm conventional brick flue If a flue liner is used it must be a minimum of 125mm diameter The...

Page 9: ...uel the flue must be swept clean prior to installation All flues should be inspected for soundness and freedom from blockages 3 8 If the fireplace opening is an underfloor draught type it must be seal...

Page 10: ...a bath or shower or where steam is regularly present 3 14 An extractor fan may only be used in the same room as this appliance or in any area from which ventilation for the appliance is taken if it d...

Page 11: ...t touch the surround See figure 4 We suggest that the actual surround is used as a template to mark the area for combustible cladding removal and that this area is increased by at least 2mm all round...

Page 12: ...shut the appliance down if an unacceptable amount of harmful products of combustion accumulate Under no circumstances should the A S D be altered or bypassed in any way Only a genuine manufacturers re...

Page 13: ...surround 1 Firefront casting 1 Front cover casting Remove all the items carefully to prevent damage Take special care when handling the ceramic components Some items may be contained in the packaging...

Page 14: ...ogether with secondary fixing to the fireplace floor The methods are detailed in section 9 of this manual Before selecting the retention method consult with the customer Method 2 is provided for insta...

Page 15: ...ng to install it is worth checking that the ignition system performs satisfactorily Set the control knob to the off position Depress the control knob and rotate it anticlockwise to the pilot ignition...

Page 16: ...n by the Debris catchment area Note that the areas are different for fireplaces with conventional brick flues and precast flues 2 Place the template on the fireplace floor printed side upward with the...

Page 17: ...n seals to the bottom edges of the convection box side flanges See figure 9 IMPORTANT Before continuing with the installation of this gas fire the aeration setting on the burner must be checked The ae...

Page 18: ...pliance is supplied with a flue restrictor for use where the flue draught is excessive The restrictor must not be fitted where a precast flue or a 125mm flue liner is used For flue liners greater than...

Page 19: ...rawlplug into each hole 6 Place the convector box back in position in the fireplace 7 Fit a woodscrew through each hole in the convector box flanges and tighten to seal the box to the fireplace surrou...

Page 20: ...the holes See figure 15 Give the cables a pull so that they grip against the convection box flanges 6 Thread the cables through the upper eyebolts in the rear wall and then through the lower eyebolts...

Page 21: ...e tension on the cables by slackening the screws and turning the hexagonal adjusters fully anticlockwise The convection box should then automatically realign itself Pull each cable taut again and push...

Page 22: ...the pilot ignition position A click will be heard as the integral piezo operates A spark should be seen between the electrode and pilot tip 2 Turn the control knob clockwise to the Off position Repea...

Page 23: ...checking turn off the appliance Remove the pressure gauge and replace the test point sealing screw 3 Relight the appliance Turn to the maximum output position and test around the sealing screw for gas...

Page 24: ...e amount of movement will be negligible See figure 22 2 Place the front base coal in the firebox with its bottom front locating over the front rim of the firebox Pull the coal forward so that it locat...

Page 25: ...n the front and rear base coals as shown in figure 25 The letter B should be upright 5 Place a type A coal between the front and rear base coals with the letter A upright The top of the coal should re...

Page 26: ...sting so that it rests on the hearth See figure 29 Black chrome front casting Place the fire front casting in front of the appliance 2 Place the bottom front cover casting in position below the fire f...

Page 27: ...htly to get past the pilot ignition position The main burner should now light Depress the control knob slightly to release from the HIGH position and turn back clockwise to LOW While turning the burne...

Page 28: ...n repeat the test If the smoke is still not drawn into the appliance inspect the sealing to the fireplace surround If the sealing is satisfactory but the appliance is installed with the flue restricto...

Page 29: ...e fire 3 Explain to the customer that the appliance has a flame failure and spillage monitoring system Point out the explanation of this system shown in the owner s guide Advise that if the fire goes...

Page 30: ...let T connector incorporates an isolating valve It is recommended that at least once a year the appliance is disconnected and the fireplace opening checked and cleared of any debris This product uses...

Page 31: ...st the aeration setting loosen the two aeration shutter screws slide the aeration shutter to the position shown in figure 31 and tighten the fixing screws 17 2 To Remove the Fire Front Surround 1 Remo...

Page 32: ...he pilot unit 4 Detach the thermocouple from the gas valve 5 Detach the electrode lead from the underside of the electrode tab 6 Remove the two screws securing the pilot unit See figure 34 7 Refit in...

Page 33: ...t 10 Remove the gas valve 11 Refit in the reverse order 17 6 To Replace the Burner See figure 36 1 Remove the burner unit See section 17 3 2 Support the elbow injector and unscrew the injector nut 3 R...

Page 34: ...fire retention is as method 1 See section 9 1 of installation instructions remove the screws If the fire retention is as method 2 See section 9 2 of installation instructions slacken the hexagonal ad...

Page 35: ...Gas tap spark generator 1 3002983 C Spark generator and circlip 1 5108923 D Control knob 1 0545979 E Pilot unit For Natural Gas Appliances Pilot injector RBM 180 02 For Propane Appliances 1 3002988 51...

Reviews: