possible, upstairs rooms and loft spaces for signs of escaping smoke indicating a
defective flue. If there is not a definite flow warm the flue for a few minutes and repeat
the smoke pellet test. If there is still no definite flow the flue may need remedial work –
Do not fit the appliance until there is a definite flow through the flue.
6. IGNITION CHECK
Before attempting to install, it is worth checking that the ignition system performs
satisfactorily.
Set the control knob to the off position.
Depress the control knob and rotate it anticlockwise to the pilot ignition position. A
'click' will be heard as the integral piezo operates. A spark should be seen between the
electrode and pilot tip
.
If there is no spark check the following: -
!
Ensure that the electrode lead is connected to the terminal at the base of the
electrode.
!
If the above is correct, check for damage to the
electrode lead.
Page 15
INSTALLER GUIDE
Figure 7. Ignition operation