35
QUALIFIED
INSTALLER
8-5/8”
42”
32-3/8”
18”
3” intake
3” exhaust collar
on the centerline
Flashing
2 x 3”
liners
3” min.
bend radius
Co-linear
adapter
2 x 3”
liners
1156
Co-linear
adapter
Engine
Approved co-linear
termination or approved
co-linear adapter
and approved
co-axial
termination
Co-Linear installation into existing F/P
9-3/8”
11-11/16”
3” exhaust
collar
1-1/2”
4” exhaust
collar adapter
FRONT
REAR
1156CLA Co-Linear Vent Adapter
4”
Conversion to Co-Linear Liners using
Valor 1156CLA Co-Linear Adapter
Co-linear portion of vent system may only be installed
within a solid-fuel burning
fi
replace and chimney.
The appliance must not be connected to a chimney fl ue
serving a separate solid-fuel burning appliance.
Requires the Valor Co-Axial to Co-Linear appliance
Adapter 1156CLA, two lengths of 2-ply 3” dia. fl exible
chimney liner approved for venting gas appliances,
a co-linear termination kit and fl ashing or a co-linear
to co-axial adapter and either a high wind vertical
vent terminal cap or a low profi le vertical termination.
Firebox zero clearance stando
ff
s supplied with the
heater are not required for this application
.
Rules for Co-Linear Venting
• Maximum 40 feet vertical pipe
• Minimum 10 feet vertical
• Maximum off set 8 feet with liners at minimum
45 degrees from horizontal plane
• Restrictor: Use #4 position for all co-linear
installations—refer to page 32 for restrictor
positioning.
Dimensions with co-linear adapter
Dimensions shown are with Valor 1156 co-linear
adapter.
Installation
For installation of the adapter to the appliance, see the
instructions supplied with the 1156CLA.
Co-Linear Venting
Any fi nishes
applied
around the
fi replace
must be non-
combustible