INSTALLER’S GUIDE
Page 26
Figure 38 Casting screw position
Fig. 39 Fire front casting
location
13.3
Flame Supervision & Spillage Monitoring System
This pilot unit includes a system which will automatically shut off the gas supply if the
pilot flame goes out or if there is insufficient oxygen due to spillage or poor ventilation.
Check that the system operates properly as follows;
1.
Light the appliance. Set the slide control to the maximum burning position and leave
for one minute.
2.
Slide the control to the off (“O”) position to extinguish the pilot.
Note the time when
the pilot goes out
.
Listen for a snap sound at the gas tap.
Note the time when the sound
is heard
.
This sound is caused by an electromagnetic valve shutting off the gas supply
through the tap. The valve is located in the body of the tap. The valve should operate
within 60 seconds of the pilot going out
.
If the valve does not operate within this time
limit do not allow the appliance to be used until the fault has been corrected.
This monitoring system must not be adjusted, bypassed or put out of operation.
This monitoring system, or any of its parts, must only be exchanged using
authorised parts.
1 4 F R O N T C A S T I N G S I N S T A L L A T I O N
1.
Check that the two screws in the back of the fire
front casting are in the outer threaded holes. If they
are in the inner holes, relocate them. See figure 38.
2.
Locate the two screw heads through the keyhole
slots at the inner sides of the surround. If the screw
heads do not project enough or project too far, the
screws can be adjusted. Lower the casting so that it
rests on the hearth. See figure 39.
3.
Fit the “ash pan” cover below the front casting
locating it as shown in figure 40.
Figure 40 “Ash pan” cover location