Ground the binary output cable shield to Terminal earth at the control system side.
Depending on factory-specific instructions, Shield can be disconnected from the Bridge
Shield terminal. In some cases, connecting the shield to Bridge Shield terminal may
improve immunity to electrical noise.
Binary output 1
Binary output 2
None
None
Alarm
Alarm
Warning
Warning
8.6 Connecting the sensor cable
When connecting the sensor cable,
make sure that the connectors are
correctly aligned. Make sure that the
connector goes correctly into its
thread, and use only your fingers to
tighten it. When correctly aligned the
connector can be screwed manually
all the way in, ensuring a good con-
tact.
If the connector is not properly
aligned, some of the thread remains
visible and the thread may be dam-
aged if the connector is forced deep-
er. Poor cable connection may cause
"Sensor Communication Error" mes-
sages.
Operating terminal | 28 (93)
K17122 V1.1 EN - 1 - 06/2020