VALLOX 90 SE

6

INSTRUCTIONS FOR USE

Remember!

Switch post-heating off when it gets too
warm in the dwelling.
Switch post-heating on again when it gets
cooler in autumn.

2.9. Supply air constant temperature control

• VALLOX 90 SE has a relative post-heating control; when the temperature selected

exceeds supply air temperature by more than 2.5˙C, the radiator is on 100%, and
when the temperature difference gets smaller, the period of active operation is
automatically reduced in two-minute sequences. The adjustment range of heating is
10...30˙C.

• The heating radiator is on when the ( )  sign is displayed.
• Temperature control is only active when post-heating has been switched on.

2.10. Supply air cascade control

• Supply air temperature control can be changed into cascade control.
• It changes the controlling principle of the post-heating radiator. The temperature of air

blown to the ventilation zone is controlled on the basis of extract air.

• The program tries to keep supply air temperature at a value determined by the

difference between extract air and the setpoint as follows: if extract air is warmer than
the setpoint, supply air temperature is lower than the setpoint by the difference. If
extract air is cooler, supply air is warmer by the difference. As an example, if room
temperature is 25˙C and the setpoint 24˙C, the aim is to blow 23˙C air to the
ventilation zone. If the temperature in the ventilation zone is 24˙C and the setpoint is
25˙C, the aim is to blow 26˙C air to the ventilation zone.

• The aim is to keep the temperature of air blown to the ventilation zone always

between 10...30˙C.

• Cascade control can be selected at the control panel, and it is active when post-

heating has been switched on.

• The heating radiator is on when the ( ) sign is displayed.

2.11. Heat recovery bypass function

• The bypass function tries to get as cool supply air as possible to the ventilation zone

by comparing the measuring results of the outdoor air and extract air sensors.

• The heat recovery cell is bypassed when post-heating is switched off, outdoor air

temperature is two degreees more than the setpoint and extract air is warmer than
outdoor air.

• The setpoint can be changed between 0…+25˙C. (Factory setting 12˙C.)

2.12. Heat recovery defrost function and preheating

• Defrost prevents the heat recovery cell from freezing, thus ensuring proper ventilation

even in cold periods.

• In VALLOX 90 SE defrosting is implemented by intermittently stopping the supply air

fan. The stopping function is controlled on the basis of the temperature sensor
measuring the temperature of exhaust air after the heat recovery cell.

• The supply air fan stops when exhaust air temperature falls below +3˙C and starts

when exhaust air temperature has risen to the value set (the amount corresponding to
hysteresis, factory s3˙C. See sections 3.3.19 and 3.3.20).

Preheating

• VALLOX 90 SE is also equipped with an electric preheating radiator. The preheating

radiator enables the defrosting of the heat recovery cell without the stopping of the
supply air fan.

 If you wish to use the preheating radiator, you have to change the setpoint for

preheating to +5˙C (factory setting is –3˙C, see section 3.3.21

).

• The preheating radiator switches on before the stopping of the supply air fan and

heats cold outdoor air, thereby preventing the heat recovery cell from freezing.

2.13. Maintenance reminder

• The maintenance reminder switches on the maintenance reminder symbol ( ) in the

main display of the control panel at defined intervals, the factory setting being 4
months.

• The maintenance reminder symbol is acknowledged at the control panel (see the

instructions for using the control panel, section 3.3.7.).

• The interval can be set between 1...15 months at the control panel.

Summary of Contents for 90 SE Series

Page 1: ...AY 1 09 332E 10 4 2009 Code 3520 VALLOX Direct current fan model C326 05 INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX 90 SE R VALLOX 90 SE L CODE 3520 SUPPLY AND EXTRACT AIR VENTILATION WITH HEA...

Page 2: ...90 SE L With direct current fans VTT certificate number Direct current fan model C326 05 Pre post heating radiator Preheating radiator electric max 900 W standard Post heating radiator electric max 90...

Page 3: ...approximately 45 Humidity content is lower in winter and higher in summer and autumn Dust mites thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter...

Page 4: ...eed Ventilation power cannot be set lower than the basic fan speed When carbon dioxide and or relative humidity adjustments are activated power cannot be adjusted higher than the maximum fan speed Whe...

Page 5: ...speed In humidity control fan speed varies between the basic and maximum fan speeds selected When the unit is taken into use for the first time with automatic setpoint search selected factory setting...

Page 6: ...1 Heat recovery bypass function The bypass function tries to get as cool supply air as possible to the ventilation zone by comparing the measuring results of the outdoor air and extract air sensors Th...

Page 7: ...speed for 45 minutes The function is started at the main display of the control panel by simultaneously pressing and holding down the and buttons for 2 seconds The function can also be started at a s...

Page 8: ...ttings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward 6 Scrolling down With this button you c...

Page 9: ...tment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval 10 The maintenance remin...

Page 10: ...ure is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operating temperature of heat r...

Page 11: ...lowered back to 4 Move the cursor with the arrow keys and change values with the and buttons Note that Exit and saving are done when the programming is finished by moving the cursor below the word Exi...

Page 12: ...ff before it is possible to start removing the cell When the sealing ledge has been removed the HR cell can be pulled out of the unit Note The laminas of the HR cell are very thin and get easily damag...

Page 13: ...ut Finally disconnect the quick coupling of the fan conductor Removing the extract air fan B The fan is attached to the fixing plate with a butterfly nut Loosen the butterfly nuts and lift the fan out...

Page 14: ...n stop ping and starting See the instructions for using the control panel section 3 3 19 The maintenance reminder symbol is displayed and the unit operates otherwise normally The maintenance reminder...

Page 15: ...l The door switch may be broken or the door is possibly not quite closed The unit is out of power e g because a fuse has blown The glass tube fuse located in the control card behind a protecting plate...

Page 16: ...VALLOX We reserve the right to make changes without prior notification 1 09 332E 10 4 2009 PDF VALLOX 90 SE Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com...

Page 17: ......

Reviews: