background image

DIGIT 

SED

ELECTRONIC CONTROLLER
WITH LCD DISPLAY

VALLOX 90 SE

4

INSTRUCTIONS FOR USE

2.  Instructions for using VALLOX 90 SE

For indoor air to stay healthy and beneficial also for the structures of the dwelling, ventilation
has to be in operation continually. It is not advisable to stop ventilation even for longer
holidays, because it makes indoor air stuffy. Also, during the heating season indoor air
humidity may condense in the ducts and structures and therefore cause humidity damage.
The sensors automatically adjust ventilation to an optimal level even if the dwelling is empty.

2.2.   Ventilation control

The unit can be fully controlled with the control panel delivered with the unit or with an
optional LON converter.
The standard week clock control can be used to control the fan power of the unit and the
setpoint for supply air temperature.
Furthermore, demand controlled ventilation can be adjusted with optional carbon dioxide
and humidity sensors.
The fan power of the unit can also be controlled with a voltage or current signal.

2.3. Ventilation control with control panel

The control panel can be used for the following ventilation control functions:

Functions for adjusting ventilation power

•  Starting and stopping.
•  Power adjustment (8 positions).
•  Setting the basic fan speed and the maximum fan speed.

Ventilation power cannot be set lower than the basic fan speed. When carbon dioxide
and/or relative humidity adjustments are activated, power cannot be adjusted higher
than the maximum fan speed.  When humidity and carbon dioxide adjustments are
switched off, fan speed can be raised to speed 8.

Supply air temperature adjustment functions (post-heating radiator is optionai)

•  Switching the electric post-heating unit on / off.
•  Setting the desired supply air temperature (+10˚C...+30˚C).
•  Selecting the method for controlling the desired supply air temperature (constant temperature

control, cascade control of temperature ).

Preheating

• Setting the control temperature for the preheating unit (-6˚C...+15˚C exhaust air).
• Changing the setpoints.

There may be three control panels at most. When two or more control panels are used,
the most recent control function is valid.

2.1.  Making the unit ready for operation

1.  Connect the plug to the mains supply. VALLOX 90 SE is now ready for operation.
2.  Turn the unit on and choose a suitable power of ventilation at the control panel. There

are either one or more control panels. See the instructions for using the control panel in
sections 3.2. 1. and 3.2.2.

In normal conditions 

basic ventilation

 with change of air every two hours is sufficient in living

areas. Boosting is needed during for example sauna baths, cooking, clothes washing or
family parties. If a carbon dioxide and/or humidity sensor is installed in the system, VALLOX
90 SE will also take care of demand controlled ventilation.

Summary of Contents for 90 SE Series

Page 1: ...AY 1 09 332E 10 4 2009 Code 3520 VALLOX Direct current fan model C326 05 INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX 90 SE R VALLOX 90 SE L CODE 3520 SUPPLY AND EXTRACT AIR VENTILATION WITH HEA...

Page 2: ...90 SE L With direct current fans VTT certificate number Direct current fan model C326 05 Pre post heating radiator Preheating radiator electric max 900 W standard Post heating radiator electric max 90...

Page 3: ...approximately 45 Humidity content is lower in winter and higher in summer and autumn Dust mites thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter...

Page 4: ...eed Ventilation power cannot be set lower than the basic fan speed When carbon dioxide and or relative humidity adjustments are activated power cannot be adjusted higher than the maximum fan speed Whe...

Page 5: ...speed In humidity control fan speed varies between the basic and maximum fan speeds selected When the unit is taken into use for the first time with automatic setpoint search selected factory setting...

Page 6: ...1 Heat recovery bypass function The bypass function tries to get as cool supply air as possible to the ventilation zone by comparing the measuring results of the outdoor air and extract air sensors Th...

Page 7: ...speed for 45 minutes The function is started at the main display of the control panel by simultaneously pressing and holding down the and buttons for 2 seconds The function can also be started at a s...

Page 8: ...ttings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward 6 Scrolling down With this button you c...

Page 9: ...tment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval 10 The maintenance remin...

Page 10: ...ure is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operating temperature of heat r...

Page 11: ...lowered back to 4 Move the cursor with the arrow keys and change values with the and buttons Note that Exit and saving are done when the programming is finished by moving the cursor below the word Exi...

Page 12: ...ff before it is possible to start removing the cell When the sealing ledge has been removed the HR cell can be pulled out of the unit Note The laminas of the HR cell are very thin and get easily damag...

Page 13: ...ut Finally disconnect the quick coupling of the fan conductor Removing the extract air fan B The fan is attached to the fixing plate with a butterfly nut Loosen the butterfly nuts and lift the fan out...

Page 14: ...n stop ping and starting See the instructions for using the control panel section 3 3 19 The maintenance reminder symbol is displayed and the unit operates otherwise normally The maintenance reminder...

Page 15: ...l The door switch may be broken or the door is possibly not quite closed The unit is out of power e g because a fuse has blown The glass tube fuse located in the control card behind a protecting plate...

Page 16: ...VALLOX We reserve the right to make changes without prior notification 1 09 332E 10 4 2009 PDF VALLOX 90 SE Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com...

Page 17: ......

Reviews: