background image

VALLOX 90 SE

12

MAINTENANCE INSTRUCTIONS

REMEMBER!

Clean the filters at least twice a year. Set the maintenance reminder interval according
to your needs. See the instructions in section 3.3.18 (dependent on the cleanliness of
outdoor and indoor air).

T

C

A

D

B

4.    MAINTENANCE INSTRUCTIONS
4.1. Before starting maintenance operations

When you open the door of the VALLOX 90 SE unit, the safety switch (S) switches the unit
off; in spite of that, please disconnect the plug of the unit. Always disconnect the plug
before starting maintenance operations for the VALLOX 90 SE unit. The post- and preheating
radiators of the unit are PTC resistors.
When they are in operation, they have an alternating voltage of 230 V on the surface.
Because of this, the plug must always be disconnected before starting maintenance
operations.

The fine filter (B) is not washable. Clean it at the same time as the G3 class filters by
vacuuming it with a brush nozzle. When cleaning, be careful no to break filter material.

To ensure good supply air quality, replace the filter preferably every year, and at least every two years
depending on local air quality.

 It is recommended to replace filters in autumn. This way the filters

stay cleaner through the winter and can effectively filter off dust in the following spring.
In connection with the cleaning of the filters it is also advisable to check the cleanliness of
the heat recovery (HR) cell (D) at about two-year intervals. The sealing ledge (E) above the
HR cell must be torn off before it is possible to start removing the cell. When the sealing
ledge has been removed, the HR cell can be pulled out of the unit. Note! The laminas of
the HR cell are very thin and get easily damaged. The correct way to remove the HR cell
is to put your hands behind the HR cell and slowly pull the cell outward. If the HR cell is
dirty, soak it in a solution of water and washing-up liquid. Rinse the HR cell clean with a
jet of water.  When all the water has drained off from between the laminas, you can put
the HR cell back in place. Finally, push the sealing ledge in place.

4.2. Filters

When the maintenance reminder lights up the control panel indicator,
the cleanliness of the filters must be checked. Outdoor air is filtered
in the unit with two kinds of filters. A G3 class coarse filter (A) filters
off insects, heavy pollen and other dust. An F7 class fine filter (B)
filters off invisible dust. Extract air is filtered with a G3 class coarse
filter (C). Clean the coarse filters A and C by 

washing them at least

twice a year.

Wash the filters with +25…30˚C warm water and washing-up liquid,
pressing them smoothly. Do not handle the filters with force.
When washing is done properly, filters stand cleaning 3 to 4 times.
In other words, you have to 

replace them at least every two years.

VALLOX 90 SE filters and heat recovery cell. The
units are available in right and left handed
models.  In the right handed model (model R)
outdoor air comes to the unit from the right side
of the centre line as shown in the instructions.
In the left handed model (model L) outdoor air
comes from the left side of the unit. The filters,
summer / winter damper and the heating ra-
diator change places correspondingly.

E

Summary of Contents for 90 SE Series

Page 1: ...AY 1 09 332E 10 4 2009 Code 3520 VALLOX Direct current fan model C326 05 INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX 90 SE R VALLOX 90 SE L CODE 3520 SUPPLY AND EXTRACT AIR VENTILATION WITH HEA...

Page 2: ...90 SE L With direct current fans VTT certificate number Direct current fan model C326 05 Pre post heating radiator Preheating radiator electric max 900 W standard Post heating radiator electric max 90...

Page 3: ...approximately 45 Humidity content is lower in winter and higher in summer and autumn Dust mites thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter...

Page 4: ...eed Ventilation power cannot be set lower than the basic fan speed When carbon dioxide and or relative humidity adjustments are activated power cannot be adjusted higher than the maximum fan speed Whe...

Page 5: ...speed In humidity control fan speed varies between the basic and maximum fan speeds selected When the unit is taken into use for the first time with automatic setpoint search selected factory setting...

Page 6: ...1 Heat recovery bypass function The bypass function tries to get as cool supply air as possible to the ventilation zone by comparing the measuring results of the outdoor air and extract air sensors Th...

Page 7: ...speed for 45 minutes The function is started at the main display of the control panel by simultaneously pressing and holding down the and buttons for 2 seconds The function can also be started at a s...

Page 8: ...ttings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward 6 Scrolling down With this button you c...

Page 9: ...tment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval 10 The maintenance remin...

Page 10: ...ure is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operating temperature of heat r...

Page 11: ...lowered back to 4 Move the cursor with the arrow keys and change values with the and buttons Note that Exit and saving are done when the programming is finished by moving the cursor below the word Exi...

Page 12: ...ff before it is possible to start removing the cell When the sealing ledge has been removed the HR cell can be pulled out of the unit Note The laminas of the HR cell are very thin and get easily damag...

Page 13: ...ut Finally disconnect the quick coupling of the fan conductor Removing the extract air fan B The fan is attached to the fixing plate with a butterfly nut Loosen the butterfly nuts and lift the fan out...

Page 14: ...n stop ping and starting See the instructions for using the control panel section 3 3 19 The maintenance reminder symbol is displayed and the unit operates otherwise normally The maintenance reminder...

Page 15: ...l The door switch may be broken or the door is possibly not quite closed The unit is out of power e g because a fuse has blown The glass tube fuse located in the control card behind a protecting plate...

Page 16: ...VALLOX We reserve the right to make changes without prior notification 1 09 332E 10 4 2009 PDF VALLOX 90 SE Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com...

Page 17: ......

Reviews: