background image

1

2 3

4

Separate cooker hood (most often in detached houses)

If there is a cooker hood independent of the ventilation system in the dwelling, only use it when
needed. Using it does not affect the operation of the ventilation unit, because the unit replaces
air in other rooms. There is in this case minor ventilation in the kitchen connected to the ventilation
unit. The unit is controlled with a separate control centre.

Cooker hood LTX

Control centre with a separate switch

© VALLOX • We reserve the right to make changes without prior notification.

VALLOX 75/95

6

INSTRUCTIONS FOR USE

Adjustment of the power of ventilation

VALLOX 75 and VALLOX 95 ventilation  units can be controlled with either a cooker hood or
a separate control centre.

Cooker hood control

The cooker hood is connected to the ventilation unit and is used to control air circulation in the
whole dwelling. Four power ranges are available.

Speed 1.

Use during absence. When the dwelling is empty,
ventilation can temporarily be diminished.

Speeds 2 and 3.

These are speeds that are normally used.
Speed 2 is used when the need of
ventilation is fairly small and air is good.
Speed 3 is used when there is a need for boosting,
for instance in the following situations: cooking,
taking a sauna bath, drying clothes, use of toilet,
guests, excess heat and "large dwellings".

Speed 4.

This boosting position is used as needed, for example during
cooking, parties and hot weathers.

Cooking

Open the flap of the cooker hood during cooking. At other times,
the flap must be kept closed. An open flap decreases the power
of ventilation in other rooms.
There are different kinds of cooker hoods. For more details, see
the instructions of the hood in question.

Separate control centre

The regulator (switch) is only used to control the ventilation unit. There are four power ranges
available.

Speed 1.

Use during absence. When the dwelling is empty, ventilation can temporarily be diminished.

Speeds 2 and 3.

These are speeds that are normally used.
Speed 2 is used when the need of ventilation is fairly small and air is good.
Speed 3 is used when there is a need for boosting –  for instance in the following situations:
cooking, taking a sauna bath, drying clothes, use of toilet, guests, excess heat and "large
dwellings".

Speed 4.

Boosting position, used as needed for example during cooking, parties and hot weathers.

Cooking

Cooking fumes are taken out with a cooker hood or an integrated hood and ventilator.
For more instructions, see the instructions of the equipment in question.
Detailed instructions for special control centres are available.

The table on the preceding page
indicates rated speeds and air
flows for dwellings of different
sizes.

The table also indicates the total
electricity consumption of the fans
at each speed.

Summary of Contents for 75

Page 1: ...INSTRUCTIONS FOR USE AND MAINTENANCE 1 09 292E 13 02 07 VALLOX For blocks of flats terraced houses and detached houses Supply and extract air ventilation with heat recovery Type 3510...

Page 2: ...rying fa cilities during these activities Sleeping Ventilation in a bedroom has to be suffi cient throughout the night The level is cor rect when air does not smell fusty when you enter the room in th...

Page 3: ...thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter water condenses in the cold structures of the house and mould starts to form The recommended maxi...

Page 4: ...ered before taking it in to the dwelling A coarse filter first removes the biggest litter particles thereby preventing the system from getting dirty After that air passes through a fine filter which c...

Page 5: ...during for example sauna baths cooking clothes washing or family parties If the user does not know the measured air flows the adjacent table shows approximate extract air flows as well as the total e...

Page 6: ...toilet guests excess heat and large dwellings Speed 4 This boosting position is used as needed for example during cooking parties and hot weathers Cooking Open the flap of the cooker hood during cooki...

Page 7: ...g supply air The temperature of supply air is adjusted at the thermostat regulator located inside the unit Adjustment range of temperature is approximately 0 25 C It is advisable to set the thermostat...

Page 8: ...at at 0 C position so that the radiator will not heat If needed the setpoint value of the water radiator thermostat shall also be reduced Defrosting Water condensing from extract air may freeze in the...

Page 9: ...filter material To ensure good supply air quality replace the filter from every six months toyear more often if needed depending on local air quality It is recommended to replace filters in autumn Thi...

Page 10: ...amper in the VKL model Unfastening and fastening of the thermostat part of the self actuated valve A B C Put the hook on the edge of the damper Y under the back edge of the fastening collar K of the f...

Page 11: ...he ceiling or the wall caused by the flow coming from the valve Cooker hood connected to the ventilation unit The most important object of maintenance is the grease filter To ensure sufficient absorpt...

Page 12: ...outdoor temperatures no humidity no freezing you can move the sensor further away from the cell An expert may also adjust the thermostat in the connection box by turning its spindle clockwise to 10 C...

Page 13: ......

Reviews: