INSTRUCTIONS FOR USE

5

Initial adjustment

The ventilation system works properly when air flows in the rooms have been measured and
adjusted with the valves in accordance with the planned values. 

After the initial adjustment, the

position of the ventilation valves must not be changed

. If there is an outlet valve with a knob in the

ceiling of the sauna, it can be adjusted as needed. The initial adjustment ensures that a
sufficient amount of air is circulated and that extract air flow is always greater than supply
air flow, i.e. the dwelling is negatively pressured compared to outdoor air. If the dwelling
is positively pressured, air in the dwelling penetrates the outer envelope of the building and
between windows, which may cause humidity damage during the heating season.

In normal conditions 

basic ventilation

 with change of air every two hours is sufficient in living

areas. Boosting is needed during for example sauna baths, cooking, clothes washing or
family parties.

If the user does not know the measured air flows, the adjacent table shows approximate
extract air flows as well as the total electricity consumption of the fans at various fan speeds.
The table also shows the fan speed that is sufficient for recommended basic ventilation in
dwellings of different sizes.

The switch positions, i.e. fan speeds, displayed in the table on a darker background are
factory preset values. If needed, an expert or electrician can change (or has changed during
the initial adjustment) settings and select speeds shown on a white background instead.
Voltage changes are also made by an expert, not the user himself.

SWITCH POSITION

1

70 V

1.1

90 V

VALLOX 95  (180 W fan)

Living area (m

2

)

Air flow (dm

3

/s)

Total electricity
consumption of
fans (W)

2

120 V

2.1

135 V

3

160 V

3.1

180 V

4

230 V

40

20

40

70

30

63

140

50

103

150

55

124

200

70

158

210

75

183

240

85

225

SWITCH POSITION

1

70 V

1.1

90 V

VALLOX 75  (105 W fan)

Living area (m

2

)

Air flow (dm

3

/s)

Total electricity
consumption of
fans (W)

2

120 V

2.1

135 V

3

160 V

3.1

180 V

4

230 V

30

15

25

45

20

38

85

30

63

110

40

78

140

50

104

150

55

128

200

70

182

Summary of Contents for 75

Page 1: ...INSTRUCTIONS FOR USE AND MAINTENANCE 1 09 292E 13 02 07 VALLOX For blocks of flats terraced houses and detached houses Supply and extract air ventilation with heat recovery Type 3510...

Page 2: ...rying fa cilities during these activities Sleeping Ventilation in a bedroom has to be suffi cient throughout the night The level is cor rect when air does not smell fusty when you enter the room in th...

Page 3: ...thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter water condenses in the cold structures of the house and mould starts to form The recommended maxi...

Page 4: ...ered before taking it in to the dwelling A coarse filter first removes the biggest litter particles thereby preventing the system from getting dirty After that air passes through a fine filter which c...

Page 5: ...during for example sauna baths cooking clothes washing or family parties If the user does not know the measured air flows the adjacent table shows approximate extract air flows as well as the total e...

Page 6: ...toilet guests excess heat and large dwellings Speed 4 This boosting position is used as needed for example during cooking parties and hot weathers Cooking Open the flap of the cooker hood during cooki...

Page 7: ...g supply air The temperature of supply air is adjusted at the thermostat regulator located inside the unit Adjustment range of temperature is approximately 0 25 C It is advisable to set the thermostat...

Page 8: ...at at 0 C position so that the radiator will not heat If needed the setpoint value of the water radiator thermostat shall also be reduced Defrosting Water condensing from extract air may freeze in the...

Page 9: ...filter material To ensure good supply air quality replace the filter from every six months toyear more often if needed depending on local air quality It is recommended to replace filters in autumn Thi...

Page 10: ...amper in the VKL model Unfastening and fastening of the thermostat part of the self actuated valve A B C Put the hook on the edge of the damper Y under the back edge of the fastening collar K of the f...

Page 11: ...he ceiling or the wall caused by the flow coming from the valve Cooker hood connected to the ventilation unit The most important object of maintenance is the grease filter To ensure sufficient absorpt...

Page 12: ...outdoor temperatures no humidity no freezing you can move the sensor further away from the cell An expert may also adjust the thermostat in the connection box by turning its spindle clockwise to 10 C...

Page 13: ......

Reviews: