OPERATING INSTRUCTION
Parameters
Parameter Name
Description
Value
Interval
Standard
Value
P67
Re-Heat function time
Compressor function time in the Re-Heat function in minutes.
1 - 20
5
P68
Re-Heat inactivity time
Re-Heat inactivity time in minutes.
5 - 255
5
P69
Inverts information on the display
Information on the upper floor goes to the right side of the display and the
information on the lower floor goes to the left side.
• 0: standard display
• 1: inverted display
0 - 1
0
P70
Select Single or Double Deck
Configuration being used:
• Double Deck (0).
• Single Deck (1).
0 - 1
0
P71
Second CAN network
0 - Disabled extra communication
1 - Enabled second CAN network
2 - Enabled Marcopolo CAN protocol
0 - 2
0
P72
Temperature reading offset
Adjusts ADC points to compensate reading
0 - 255
25
P73
Maximum time function is enabled
Re-Heat
Maximum time the function will be enabled in minutes
0 - 255
25
P74
High pressure transducer
Enables or disables pressure reading by transducers
• 0: Sensors disabled;
• 1: Sensors enabled.
0 - 1
0
P75
Low pressure transducer
Enables or disables pressure reading by transducers
• 0: Sensors disabled;
• 1: Sensors enabled.
0 - 1
0
P76
AC purifier UV disinfection system
Enables UV purifier AC system fault detection (disables CAN address selection)
• 0: UV purifier AC disabled (addressing available)
• 1: UV purifier AC enabled (addressing unavailable)
0 - 1
1
CC 430 P3
23