OPERATING INSTRUCTION
Parameters
Parameter Name
Description
Value
Interval
Standard
Value
P39
Controller parameter of the
Proportional motor water valve.
P and I portion of the proportional motor water valve controller.
0 - 255
60
P40
Reserved
-
-
-
P41
Auto Start
Automatically turns the controller on when the engine is running.
• 0: Automatic Start OFF
• 1: Automatic start ON
0 - 1
0
P42
No ventilation below the set-point.
Turn off ventilation when the room temperature is below the set-point.
• 0: ventilation always active
• 1-99: turns ventilation off at the selected value minus the set-point.
0 - 99
0
P43
No ventilation below the set-point:
temporary ventilation ON.
In the case of (P42> 0), it turns on the ventilation when the ambient
temperature is well below the set-point for a few seconds. Ventilation ON, in
seconds.
10 - 255
15
P44
No ventilation below the set-point:
temporary ventilation OFF.
In the case of (P42> 0), it turns on the ventilation when the ambient
temperature is well below the set-point for a few seconds.
10-255: ventilation OFF, in minutes.
10 - 255
15
P45
Convection heating on the floor.
Floor heating availability
• 0: not available
• 1: available
0 - 1
1
P46
Reserved.
-
-
-
P47
Reserved.
-
-
-
P48
Reserved.
-
-
-
P49
Upper range Recirculation
Automatic Mode.
Hysteresis upper to the set-point for automatic air recirculation mode.
1 - 5
2
P50
Lower range Recirculation
Automatic Mode.
Hysteresis lower to the set-point for automatic air recirculation mode.
1 - 5
2
P51
Valve Recirculation Time
open.
Time in seconds for open air recirculation valve in automatic mode.
1 - 90
20
P52
Valve Recirculation Time
closed.
Time in minutes for closed valve in automatic mode.
1 - 90
60
CC 430 P3